T r o u b l e s h o o t i n g
Improper installation, inadequate insulation, or a cellar that is too large will
cause the cooling unit to run continuously and be difficult to troubleshoot.
The cooling unit is designed to turn on when the air temperature in the cellar rises
ABOVE the Minimum Set Point + Temperature Differential, and turn off when the air
temperature falls below the Minimum Set Point. For example, if the Minimum Set
Point is 58°F and the Temperature Differential is 4°F, the cooling unit will turn above 62°F
and turn off below 58° F. In this example, the average temperature inside the cellar will
be 60°F.
Cooling Unit Runs Constantly
When bottles are first loaded in the cellar, the cooling unit will run continuously (even
up to a week) until the temperature inside the cellar falls below the Set Point.
Hot weather conditions, insufficient ventilation and/or dirty condenser coil may cause
the cooling unit to run continuously. To reduce cycle times,
1. Remove any obstructions to air flow to or from the unit
2. Check to make sure the condenser coil is clean
3. Increase the supply of cool air to the space outside the condenser coils, using a fan,
ducting or an exhaust system to remove heat from the space.
4. Raise the Minimum Set Point on the cooling unit
Cooling Unit Is Dripping
The cooling unit is designed to remove excess moisture from inside the cellar, which
collects in the drip pan of the cooling unit and is removed by the internal condensate
pump. Excess moisture can occur when the cooling unit runs constantly, when the
Minimum Set Point is too low and/or when the cellar doesn’t have a good seal from the
outside environment. To eliminate overflow, do the following:
1. Ensure the condensate pump drain line is not blocked.
2. Check that the cellar has airtight seals, including the door(s), light fixtures, and all
walls, ceiling and floor.
3. Raise the Minimum Set Point of the cooling unit.
The Cooling Unit Won’t Turn On
The cooling system is programmed with a
3-Minute Delay
at Startup
to protect its
internal components.
Summary of Contents for 3000Scm
Page 1: ...V3 3 16 Control the Elements Split Ceiling Mount Refrigeration Systems Owner sManual...
Page 6: ...6 V3 3 16 Evaporator Cut Sheets...
Page 7: ...7 V3 3 16 Condensing Unit Cut Sheets...
Page 11: ...11 V3 3 16 Evaporator Mounting Detail...
Page 18: ...18 V3 3 16...
Page 20: ...20 V3 3 16...
Page 21: ...21 V3 3 16 6000Scm Wiring Diagrams Option A Dual Power Valve Control Page 1 of 2...
Page 22: ...22 V3 3 16 6000Scm Wiring Diagrams Option A Dual Power Valve Control Page 2 of 2...
Page 23: ...23 V3 3 16 8000Scm Wiring Diagrams Option A Dual Power Valve Control Page 1 of 2...
Page 24: ...24 V3 3 16 8000Scm Wiring Diagrams Option A Dual Power Valve Control Page 2 of 2...
Page 26: ...26 V3 3 16 3000 4000Scm Wiring Diagram Option B Single Power Electronic Control...
Page 28: ...28 V3 3 16 6000Scm Wiring Diagram Option B Single Power Electronic Control Page 1 of 2...
Page 29: ...29 V3 3 16 6000Scm Wiring Diagram Option B Single Power Electronic Control Page 2 of 2...
Page 30: ...30 V3 3 16 8000Scm Wiring Diagram Option B Single Power Electronic Control Page 1 of 2...
Page 31: ...31 V3 3 16 8000Scm Wiring Diagram Option B Single Power Electronic Control Page 2 of 2...