Nome file: buchholz relay testing device                        REV. 1  DTD 17/06/2008                                                Pagina 3 di 4 
 

UNCONTROLLED COPY 

 

f)

  Open vent cock (black handle in vertical position) 

g)

  Hold the testing device by avoiding to touch cartridge 4 with hands (use a glove or a 

cloth) 

 

Since  the testing  device  is  under  pressure  the  sudden exit  of    CO

2

    from 

the cartridge (gas expansion stage) make cool the metal outside surface of 
the cartridge. 

  

h)

  Carefully open the output cock 2 of the testing device (turn it anti-clockwise) to check 

alarm  is  working  properly.  Then,  from  the  inspection  window  of  the  relay,  verify  the 
progressive emptying of its upper part, and consequently, the corresponding oil level 
lowering . As soon as the alarm is operated, close completely  the output cock 2 (turn 
it clockwise). 

 
TRIP TEST (only for EE models, English standard) 
 
EE models relays have a second cock on their lower part. Trip contact proper functioning 
can be tested by connecting the test device to this cock. 
Make  sure  that  the  cock  is  shut  (black  handle  in  horizontal  position),  then  remove  the 
protective  plug  and  screw  at  its  place  the  joint  6  and  re  open  the  cock  (black  handle  in 
vertical  position).  Quickly  open  output  cock  2  (fig.3).  When  the  sudden  gas  injection 
releases trip contact, close the output cock. 
 
 

 

Fig.3 

 

 