Nome file: buchholz relay testing device                        REV. 1  DTD 17/06/2008                                                Pagina 4 di 4 
 

UNCONTROLLED COPY 

 
REMOVAL OF TESTING DEVICE 
 
A)  Close the vent cock (black cock handle on horizontal position) on which the device is 

connected (this will  prevent oil leakage when joint 6 will be removed) 

B)  Unscrew joint 6 from the vent cock 
C)  Screw  the  protective  plug  (the  one on  the lower  part of  the  relay)  if  it has previously 

been used 

D)  Carefully open the upper vent cock to allow the exit of the gas inside the relay ; when 

the relay is full, the oil will start to flow out from the cock: shut the cock 

E)  Screw the protective plug of the vent cock. 
 
NOTES 
 
F)  In case of alarm test (partial emptying of of the  relay ) the charge inside cartridge 4 

doesn’t run completely out, the cartridge can be re-used for further alarm tests. In this 
case, please keep the cartridge inside the testing device. The level of the charge can 
easily be verified by opening the output cock 2 till some gas comes out. To perform a 
new alarm test with the cartridge still on site, please start from point d) onwards. If the 
cartridge  is  exhausted:  open  the  output  cock  to  run  completely  out  of  the  possible 
remaining  charge,  then  unscrew  cartridge  4  from  its  site  and  replace  it  starting  from 
point a).   

G)  In case of trip & alarm test (EE relays) the charge inside the cartridge is enough only 

for one test. To perform a new test of both contacts (trip & alarm) open the output cock 
2 to run completely out the remaining charge, unscrew the cartridge and proceed from 
point a). 