CE+T Power TSI VEDA User Manual Download Page 31

12.2  T1S/T2S

12.2.1  Removal

„

„

Use a small screw driver to release the latch keeping the T1S/T2S in position

„

„

Take care when inserting screw driver in T1S. If tip is not well engaged, there is a chance to damage dip switches 

„

„

Pull the module out

12.2.2  Inserting

„

„

Push the module firmly in place until the latch snaps in position 

12.3  Fan replacement

The FAN life is approx 45.000hours. The inverter modules have fan runtime meters and fan failure alarm. Fan failure can result 
from failing fan or driver circuit.

„

„

Let the module rest at least 5 minutes prior to initiating work.

„

„

The inverter front must be removed. Use a blunt tool to depress the latches on the module side fixing the front to the 
module.

„

„

Remove the fan and unplug the supply cord.

„

„

Replace with new fan and connect supply cord

„

„

Replace front, make sure that the front latch properly.

„

„

Plug in

„

„

Check fan for operation

„

„

Access T2S and reset the fan run time alarm from within the action menu

!!

31 

– TSI VEDA – User manual – v7.1

Summary of Contents for TSI VEDA

Page 1: ...ational patents and trademarks Address CE T S a Rue du Charbonnage 12 B 4020 Wandre Belgium www cet power com info cet power com SINGLE INPUT INVERTER The DC Power as default source AC BACKUP IN A DC...

Page 2: ...gn 12 7 1 Pack A la Carte 12 7 1 1 Pack 12 7 1 2 A la Carte 12 8 Installation of Veda PACK or Single shelf shelves 13 8 2 Electrical installation Veda PACK or single shelf 13 8 2 1 Pre requisites 14 8...

Page 3: ...1 Removal 30 12 1 2 Inserting 30 12 2 T1S T2S 31 12 2 1 Removal 31 12 2 2 Inserting 31 12 3 Fan replacement 31 13 AC output distribution 32 13 1 DU connection installation removal 32 13 2 Miniature C...

Page 4: ...sion REG Regular DSP Digital Signal Processor AC Alternating current DC Direct current ESD Electro Static Discharge MET Main Earth Terminal MBP Manual By pass TCP IP Transmission Control Protocol Inte...

Page 5: ...n a single action REG systems can be seen as independent power sources To comply with local and international safety standards N output and PE shall be bonded The safety standard IEC EN62040 1 1 requi...

Page 6: ...abinet by unplugging the inverters Mark inverters clearly with shelf and position for correct Empty inverter positions must not be left open Replace with module or cover 2 2 Other Isolation test must...

Page 7: ...ronic 3 1 REG mode Inverter modules carrying the TSI logo and the REG mark is a traditional converter DC in AC out Sinusoidal output converted from DC input DC input only The output voltage is always...

Page 8: ...er Inverter modules run in single phase configurations Fan is equipped with alarm and run time meter The fan is field replaceable 220 D x 139 W x 41 5 H 1 4 Kg 4 2 Sub rack The Veda shelf shall be int...

Page 9: ...A la Carte monitors max 32 inverters in one bus The T1S provides Alarm monitoring 2 outgoing alarms 2 digital input Dip switch for local setting The T2S provides Alarm monitoring Record the latest 20...

Page 10: ...optional accessory Veda is suitable for easy integration in 300 400 600 mm depth cabinet 5 2 AC distribution unit 5 2 1 Distribution Rack The standard AC output distribution is designed with a 8X 6A...

Page 11: ...oom for 1 3 display units and 1 TCP IP agent 6 1 1 Display Backlit 2 line dot matrix The display show two values simultaneous 6 1 2 TCP IP Agent The TCP IP interface board is mounted on the CanDis she...

Page 12: ...inverter modules 7 1 2 A la Carte The A la Carte is pre assembled and configured as single phase systems The system comprises cabinet inverter sub rack inverter modules monitor device T2S and AC outpu...

Page 13: ...tput distribution 2 x IEC socket with 10 Amps fuse protection 8 1 Mounting kit Veda PACK or Single shelf The mounting guide rail is adjustable to fit different kind of cabinet depths 8 2 Electrical in...

Page 14: ...erminations All cables shall be rated at Min 90 deg C Electrical terminations shall be tightened with 1 5Nm All connection are screw terminals connectors DC Input Individual per module observe polarit...

Page 15: ...Cable min Connector Torque 48VDC Veda pack 16A 2 x 1 5mm2 Screw terminal 1 5Nm VEDA is individual DC feeding On the back the terminal of and are present DC connector are wired as a couple That means t...

Page 16: ...IEC Socket protected by 10 Amps fues 48VDC 3x1 5mm2 Screw Terminal 1 5Nm 8 2 6 Signalling Relay characteristics Selectable Major Minor Switching power 60W Rating 2A at 30VDC 1A at 60VDC Max wire size...

Page 17: ...OFF The remote ON OFF can be connected to any shelf The remote ON OFF requires changeover contacts one input opens as the other close If both transitions are not picked up the status is not changed Re...

Page 18: ...d The internal bus comprise of a 6 pole ribbon cable and an 8 pole ribbon cable The internal bus connectors are sensitive and special caution should be taken during installation to keep them out of ha...

Page 19: ...e slot and raise the cabinet on location 9 3 Fixing the cabinet to the floor The cabinet is fixed through the base of the cabinet Remove lowest front cover to gain access to the fixing holes Max screw...

Page 20: ...top cover has support to strap the cables with nylon tie straps Ground PE DC Input X1 Alarm X3 X5 X6 AC Output X4 AC Output distribution X4 DC Input X11 to X18 Alarm X3 Digital in X5 Remote ON OFF X6...

Page 21: ...ound must be terminated even if commercial mains is not available According to local regulations Min 16mm2 9 4 4 DC input X1 9 4 4 1 Bulk input Common DC input per system Note Screws and nuts are not...

Page 22: ...9 4 4 2 Individual input Individual DC input per module and return Max 2 5 mm2 per connection terminal Two terminal for one shelf 22 TSI VEDA User manual v7 1...

Page 23: ...al Cable lug Screw terminal cable lug 1ph Fuse CB Min Cable mm2 Fuse CB Min Cable mm2 1 8 50A 10 3 6 100A 25 16A Live Screw terminal 1 5mm2 Common Ferrule 1 5 mm2 1 5Nm torque 5 4 160A 50 7 2 180A 70...

Page 24: ...9 4 6 Signalling All relays are in non energized position 24 TSI VEDA User manual v7 1...

Page 25: ...onnected to any shelf The remote ON OFF requires changeover contacts one input opens as the other close If both transitions are not picked up the status is not changed Digital input characteristics Re...

Page 26: ...properly Blinking green orange alternatively Recovery mode after boost 10 In short circuit condition Permanent orange Starting mode Blinking orange Modules cannot start Check T2S Blinking red Recover...

Page 27: ...undancy No Redundancy Redundancy 10 2 1 T1S alarm Description Type 1 Redundancy plus one inverter lost by Major 2 TSI Bus defect Major 3 Incompatability parameter Major 4 Main source lost see configur...

Page 28: ...S driver CET_T2S inf installed on laptop Available for download at http www acbackuptsi com Username T322010000 Password No password required enter Read T2S manual for detailed setup 11 1 Communicatio...

Page 29: ...isplay 0 Return to previous menu 1 14 Page number selection 16 Clear log 17 Save log to a file 6 Module errors information 0 Return to preceding menu 1 32 detailled Modules errors 3 System actions sel...

Page 30: ...ff when opening the handle The handle only fixes the module to the shelf Use a screw driver to release the latch of the handle Open the handle Pull the module out Replace with new module or blind unit...

Page 31: ...nverter modules have fan runtime meters and fan failure alarm Fan failure can result from failing fan or driver circuit Let the module rest at least 5 minutes prior to initiating work The inverter fro...

Page 32: ...removal Circuit breakers are normally installed from factory How to add breakers 1 Insert the short connection cable 10mm2 included in the breaker Line side and tighten Up to 40A breaker use one conn...

Page 33: ...hat all cables are strained relived Make sure that all breakers are according to recommendation and local regulations Make sure that DC polarity is according to marking Re tighten all electrical termi...

Page 34: ...bserve this rules will result not to have all module operating when running on DC Installation and commissioning must be done and conducted by trained people fully authorized to act on installation It...

Page 35: ...cording to the site LVD load on AC AC threshold level Switch OFF ACin and check if system is working on DC Not applicable for REG Module Switch ON ACin and check if system correctly transferred load o...

Page 36: ...hreshold level No output power Check output breaker All OK but I have alarm Check configuration file and correct No of modules Download clear log file No output alarm Mind the default time delay UA 60...

Page 37: ...nternal temperature for deviation between modules Temperature deviation may indicate build up of dust Clean with compressed air Check module system load Check Correct inverter mapping DC group AC grou...

Page 38: ...be requested through the http my cet power com extranet Repair registering guidelines may be requested by email at repair cet power com The RMA number should be mentioned on all shipping documents rel...

Page 39: ...19 Appendix 19 1 Cabinet foot print layout 39 TSI VEDA User manual v7 1...

Page 40: ...WANDRE T l 04 3456700 Fax 04 3456701 THIS DOCUMENT REMAINS THE PROPERTY OF CE T IT SHALL NOT BE GIVEN TO A THIRD PARTY OR REPRODUCED WITHOUT CE T s AUTHORIZATION 1 2 3 4 5 6 7 8 9 10 11 A B C D E F G...

Page 41: ......

Reviews: