BO600EVO - BO900EVO - P300EVO - P600EVO
Architectural handles
11
Step 3
,
Handle installation.
The handle is mounted on the door leaf.
Cut the screw cover into two separate parts so that the handle can be inserted (
requirement is approx. 250 mm) can be inserted into the location required.
6] FIRE SAFETY INSTALLATION - DAS
We keep the same wiring for the power supply of the maglock, you have a different wiring is required for the ins-
tallation of CMSI in a fire safety set-up (see-below).
Place the jumper on
DAS position
24/48V dc (-15%/+20%)
CMSI remote input
DAS Configuration :
- Jumper in DAS position for CMSI remote control
(Fire safety installation)
- Remote control input voltage 24/48V dc
(-15%/+20%)
Consumption for CMSI remote control
24V dc < 1 mA
48V dc < 2 mA
Fix the handle with 2 dedicated screws