FR
FR
BO600EVO - BO900EVO - P300EVO - P600EVO
Poignées bandeaux
7
EN
BO600EVO - BO900EVO - P300EVO - P600EVO
Architectural handles
1] PRODUCT PRESENTATION
- Complies with NF S61-937 (PV SD190041 - CNPP)
- Free-voltage 12/24/48V dc (-15%/+20%)
- Visual signal (blue = closed; green = open)
- Fits with all types of doors: Metal, wood, glass, PVC
- Customisation: RAL and cut
- Electromagnetic lock pre-mounted on the clip-on bracket
(mounting on door frame)
- Pre-mounted armature plate on cover handle
(mounting on door leaf)
- Partial or total recovery of old installation
- Vertical or horizontal installation
- Product installation in accordance with NF S61-932
- Product maintenance in accordance with NF S61-933
DAS Configuration:
- Jumper in DAS position for CMSI remote control
(Fire safety installation)
- Remote control input voltage 24/48V dc (-15%/+20%)
Consumption:
12Vdc : 480 mA per electromagnetic lock
24Vdc : 240 mA per electromagnetic lock
48Vdc : 120 mA per electromagnetic lock
Remote control for the CMSI
24Vdc < 1 mA
48Vdc < 2 mA
IP42
IK10
NFS61937
Recommended
Power supply
BS24
ADC324
In option:
• REO : 5 mm aluminium extension piece for door leaf and/or door frame
• ALMA : aluminium moulding for the passage of cables
60
43,4
7,7
37
63,2
43,4
8,8
30,9
28,6
2,3
105
ALMA
REO
5
5
5
D
OOR FRAME
D
OOR LEAF
2] REMINDERS AND RECOMMENDATIONS
DESCRIPTIVE DIAGRAM AND OVERVIEW
NF S61-937 Conformity
This product meets the requirements of
NF S61-937 only with a 24V or 48V dc voltage power
supplywith a SELV source.
Recommended power supplies
The architectural handle is designed for magnetic
locks of 300kg holding force each, with power supply
12/24/48V dc. Choose the right power supply accor-
ding the settings of the maglocks.
Wiring
Plan the correct cable cross-section according to the
distance between the power supply and the architec-
tural handle.
Tips for use
The architectural handle can be installed on doors by
pulling with one or two leaves, one of which is conside-
red semi-fixed. It is installed on perfectly aligned doors,
otherwise a spacer must be used. You can also reinforce
your door with an internal handle section (Ref:PRP800)
for the opposite side of your door. A cable trunking to
hide your cables in the same style (Ref: ALMA).
Reminder
The electromagnetic locks are already mount on the wall
support. The architectural handle is provided with
armature plates.
It is recommended to mount the caps on both ends
before installation.
You must fix the plastic handle with the two screws
povided with the product.
Recommended
Power supply
ADC612SB
ADC335