Primary Input (Terminals 5 and 6 of M2)
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 4÷20mA) proceed as follows:
A
B
C
A
B
C
A
B
C
Type
Input features
0
10V (default) Impedance
15K
POT
Impedance
10K
min
4
20mA
Impedance
100
17.3.1
Primary Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
Give the power supply.
With Control Panel go in the Hardware menu (
= 5)
Set the input signal to the min value (ex. 0V for 0÷10V or 4mA for 4÷20mA)
Select the parameter
then press
F
(
Flashing)
Press
Up
key (
on display)
Press
F
key to confirm (
on display)
Set the input signal to the max value (ex.10V for 0÷10V or 20mA for 4÷20mA)
Select the parameter
then press
F
(
Flashing)
Press
Up
key (
on display)
Press
F
key to confirm (
on display)
- The Input calibration procedure is done.