Installation
Before to install, make sure that the Thyristor unit
have not damages.
If the product has a fault, please contact the
dealer from which you purchased the product.
Verify that the product is the same thing as
ordered.
The Thyristor unit must be always mounted in
vertical position to improve air cooling on heat-
sink.
Maintain the minimum distances in vertical and in
horizontal as represented.
When more unit has mounted inside the cabinet
maintain the air circulation like represented in
figure.
Sometimes is necessary installing a fan to have
better air circulation.
10.1
Environmental installation conditions
Ambient temperature
0-40°C at nominal current. Over 40°C use the
derating curve.
Storage temperature
-25°C a 70°C
Installation place
Don’t install at direct sun light, where there are
conductive dust, corrosive gas, vibration or water
and also in salty environmental.
Altitude
Up to 1000 meter over sea level. For higher
altitude reduce the nominal current of 2% for each
100m over 1000m
Humidity
From 5 to 95% without condense and ice
Pollution Level
Up to 2nd Level ref. IEC 60947-1 6.1.3.2
10.2
Derating Curve