REVO S
1PH from 30A to 40A
User’s manual
15
Connection Diagram for Single-phase
INPUT
Input:
SSR
ON
T1
L1
3
LOAD
L2/N
L1
L2/N
L1
*
2
*
1
*
Note:
*
1 A suitable device must ensure that the unit can be electrically isolated from the supply, this allows the
qualified people to work in safety.
*
2 The thyristor unit must be protected by extrarapid fuses (optional). The Fuses must have I²t 20% less than
thyristor’s I²t. The warranty of thyristor is null if no proper fuses are used (see technical data).
*
3 The heat-sink must be connected to the earth.