53
12.7
Digital Output
The MULTIDRIVE thyristor unit has 4 digital output with relay contact (Max 500mA, 125Vac), an output
control the main contactor and is a normally open (NO) fixed contact, and the others output gives
indications of the alarms state, the contacts can be (NO or NC).
12.7.1
Run Relay (Terminals 9 and 10 see par. 7.4)
This digital output is used to control the main contactor, when the thyristor unit is in run the output is
active and the contact is closed.
12.7.2
Critical Alarm (Terminals 11 and 14 see par. 7.4)
This digital output is active when a critical alarm occurs (see par. 9.2).
The standard contact used for this output is normally open (NO), but is possible change the contact
type:
Caution:
this procedure must be performed only by qualified persons
Type
JP8 C/D
NO (standard)
A-B
NC
B-C
JP8 C/D
C
B