CD Automation srl
MULTIDRIVE-1PH 850A
User’s Manual
50
12.5
Analog Outputs
The MULTIDRIVE thyristor unit has 4 configurable analog outputs (0÷10V, 4÷20mA, ecc).
The output 1 is for retransmitting the average power on the three phases, and the others 3 is for the
retransmitting the RMS current on the phases L1, L2 and L3
12.5.1
Output 1: Average Power (Terminals 15 and 23 or 16 and 23 - see par. 7.4)
The average power output is already configured in line with customer requirements that are defined in
the Order Code. The Order Code is written on the identification label.
However, if you wish to change the average power output (ex. from 0÷10V to 4÷20mA) proceed as
follows:
Caution:
this procedure must be performed only by qualified persons
Type
Output features
P097
JP14
0
÷
10V
20mA Max
0
A-B
0
÷
20mA
500
Ω
Max
0
B-C
4
÷
20mA
500
Ω
Max
1
B-C
JP14
A B C
JP15
A B C
JP16
A B C
JP17
A B C
Setting the Output 1 Value
The parameter P104
allows to set the full scale value to have the maximum output,
for example if you use an indicator with full scale 50Kw set the parameter P104
= 50.