CD Automation srl
MULTIDRIVE-1PH 850A
User’s Manual
34
10.4
Setup Menu
Firing mode Selection:
This parameter selects the Firing Type.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Fir
Firing mode
Selection
Sw
1*
0
2
0
2
R/W
* if not specified in the Order Code
HB sensitivity:
This parameter defines the threshold of current that activates the HB alarm
This value is in percentage respect the nominal load value.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Hb_S
HB sensitivity
%
100,0
0
4095
0
160,0
R/W
Nominal Current 100A P066
=20. This means that the Heather Break Alarm became active when
the current goes below 80A.
Feed-back selection:
This parameter selects the Feed-back type.
Parameter
Display
Parameter
Name
Contents
UM
Default
Value
UM
Min
Value
DEC
Max
Value
DEC
Min
Value
UM
Max
Value
UM
Par.
Type
Fir
Feed-back
selection
Sw
1*
0
3
0
3
R/W
* if not specified in the Order Code
Sample Values and Note
Burst Firing
=
Phase Angle
=
Delay Trig Burst Firing
=
Sample Values and Note
Sample Values and Note
Current feed-back (rms value)
=
Voltage feed-back (rms value)
=
Power feed-back VxI
=
External feed-back
=