C.D. Automation Srl
CD-KP for CD3000E & Multidrive
User’s Manual
www.cdautomation.com
8
1.8 Default settings
CD-KP is supplied with a base configuration allowing the immediate usage without any further
configuration. Some default values are reported in the following table.
Function
Value Notes
Addressed unit
1
Baud Rate
19200
L/R key
Off
Disabled
Cmd feature in operator menu
Off
Disabled
Retransmission
Off
Disabled
Upper operator display 1
P32
Power (average on 3 phases)
Lower operator display 1
P8
Reference
Upper operator display 2
Arst
Current (average on 3 phases)
Lower operator display 2
P8
Reference
Upper operator display 3
P31
Voltage
Lower operator display 3
P8
Reference
Command menu password
255
Enabled
Calibration menu password
255
Enabled
Diagnostic menu password
255
Enabled
Setup menu password
255
Enabled
Configuration menu password
255
Enabled
By default, CDKP is configured to communicate with units at address 1 and baud rate 19200.
The variables displayed in operator menu are: average power (P32), average current (Arst
parameter), voltage and reference signal in percentage. All the menus are protected by
password with value 255.
1.9 Start-up
Before to supply the CD-KP check that the wiring is correct and verify the supply line voltage
value (120Vac or 240Vac). Automatically, the operator menu 1 will be displayed with power
value in upper display and reference value in lower display.
If an “E” is flashing in error/alarm display, there is a communication error, CD-
KP is not able to exchange data with thyristor unit. The user must verify:
- that CD-KP and thyristor unit have the same baud rate
- that the address called by CD-KP is the unit’s address
- that the polarities of RS485 link are correct
- that the thyristor unit is supplied and in ON condition.
If an “A” is flashing in error/alarm display, it means that CD-KP received an
alarm indication from the thyristor unit. The user must go in the operator
menu, scroll up to alarm sub-menu (
ALAr
), identify the alarm type and
remove its cause (see operator menu’s paragraph).
E
A
Summary of Contents for CD3000E