Installation
Caution:
Don't install near the hot elements or near the units that could give
electromagnetic interferences.
The CD3000E Thyristor unit must be always mounted in vertical position to improve air cooling on heat-
sink. Maintain the minimum distances in vertical and in horizontal as represented.
When more unit has mounted inside the cabinet maintain the air circulation like represented in figure.
Sometimes is necessary installing a fan to have better air circulation.
6.1
Environmental installation conditions
Ambient temperature
0-40°C at nominal current. Over 40°C use the
derating curve (see par. 8.1)
Storage temperature
-25°C to 70°C
Installation place
Don’t install at direct sun light, where there are
conductive dust, corrosive gas, vibration or water
and also in salty environmental.
Altitude
Up to 1000 meter over sea level. For higher
altitude reduce the nominal current of 2% for each
100m over 1000m
Humidity
From 5 to 95% without condense and ice