4.4 The Indicator Lights & Controls:
NOTE: Red and Green indicator lights only work when the
ENABLE button is depressed.
GREEN:
indicates the actuator is being commanded to
extend the CLOSE plunger.
RED:
indicates the actuator is being commanded to extend
the OPEN plunger.
YELLOW:
indicates that both plungers are retracted and the
controller and batteries are healthy.
Rapidly
blinking YELLOW
indicates the battery voltage with
zero load has fallen to an unacceptable level. Operation is
inhibited until batteries with an acceptable voltage level are
installed.
The ENABLE button:
The Enable button must be continuously depressed in
order to command the actuator.
Releasing the enable button has the same affect as
releasing both RED and GREEN pushbuttons– the actuator
will retract both plungers.
Note:
If a pushbutton is held in the trip or close position for
an extended amount of time, the plunger will remain in the
extended position. When the pushbutton or the enable
button is released, the plunger will retract.
5.0 Care and Storage
5.1 Cleaning the magnets:
Over a period of time, the magnets may attract ferrous
debris. Exercise care to avoid setting the actuator where
the magnets might attract debris. If this does occur, use a
paper towel or nylon bristle brush to clean the face of the
magnets. Keeping the magnet faces clean ensures that
maximum holding power is maintained.
5.2 Storage:
Remove all batteries from the control station if the device
will not be used for longer than 6 months.
Never store the batteries where the ambient temperature
might exceed 110º F.
Avoid getting the unit wet or storing it in a high humidity
location.