STEP 3: With actuator now flush against the MCC
door, twist each magnet lever one-half turn clockwise
to lock the magnets and actuator in place.
STEP 4: For the wireless versions of the RSK-ABL1,
the installation is complete and it is ready to operate.
See Section 4.2 for the operating procedure.
For the cabled version of the RSK-ABL1, the cable must be
installed prior to proceeding. Attach the cable to both the
actuator and the hand-held controller by inserting the
cable in the connector and turning the ferrule clockwise to
lock it in place. Once the cable is connected, see Section 4.2
for operation.
4.2 Operating the RSK-ABL1
STEP 1: Press the WAKE button to power up the actuator.
STEP 2: While standing at a safe distance, press and hold
the ENABLE button on the hand-held controller. The yellow
light should illuminate. Then press and hold the button
corresponding to the handle direction that is desired (ON
or OFF). Both the ENABLE button and the ON or OFF button
must be held simultaneously until the full stroke of the
operating handle is complete. Then the buttons can be
released and the actuator will return to its neutral position.
NOTE: The actuator will power itself OFF after a couple minutes of no use.
If it does power down, turn it back on by pressing the WAKE button.
STEP 3: When completed with operating the RSK-ABL1,
power the actuator OFF by pressing the SLEEP button.
4.3 Removing the RSK-ABL1
STEP 1: Verify that the actuator is powered OFF by pressing
the SLEEP button. DO NOT ATTEMPT TO REMOVE THE
ACTUATOR WITH THE POWER ON AS THIS COULD CAUSE
A PINCH POINT INJURY.
STEP 2: While firmly holding the actuator in your right
hand, disengage the magnets by using your left hand to
turn the magnet levers counter-clockwise. Lower the
actuator off the operating handle.
STEP 3: Disconnect cable (for cabled versions only) and
return components to carrying case or store on the side of
the MCC. (See Section 5.0 for details)