12
RS232
USB
EPO(Emergency Power OFF)
fan
Parallel Port
Output Breaker
Manual Bypass Breaker
AC Breaker
Bypass Breaker
Battery Breaker
Intelligent Slot
Front Panel
PARALLEL PORT
SINGLE
MODE
INTELLIGENT SLOT
RS232
USB
4 8 5 -
4 8 5 +
GND
EPO.
FAULT
OVER LOAD
BYPASS
A C F A U L T
BAT. LOW
PARALLEL PORT
SINGLE
MODE
INTELLIGENT SLOT
RS232
USB
4 8 5 -
4 8 5 +
GND
EPO.
FAULT
OVER LOAD
BYPASS
A C F A U L T
BAT. LOW
INPUT
N
L
J P 2
J P 1
N
L
OUTPUT
BYPASS
E
PE
E
PE
BATTERY
+
-
ENTER
O N / O F F
SCREEN
ESC
L I N E
BYPASS
B A T .
I N V .
FAULT
Free Contact
Terminal
Figure2.2
Layout of full unit
2.5
The selection of Air switch and connecting wires
The wires for different capactity of UPS should be with different grade,
unsuitable wires or air switch will easily bring dangers. The principle of selection are:
3-5A/mm
2
for middle and small size UPS, 2.5-3A/mm
2
for big power UPS. Meantime,
we should consider to control the max voltage drop no more tha n 3V.
There have input neutral wire for bypass and output neutral wire for UPS power
in the UPS midline system. For three phases in and single phase out UPS, the
cross-sectional area of input null line should be 1.5-1.7 times of phase line.
There have groundings for safe protection and lightning protection in the UPS
systerm, their cross-sectional area should be 0.5-1.0 time of phase line and no smaller
than 6mm
2
2.5.1
The selection of air switch
POWER
KVA
Input voltage
VAC
Output voltage
VAC
Input
Max.current(A)
Output
Max.current(A)
Input air
switch (A)
Output air
switch (A)
4
220
220
32
18
50
32
6
220
220
44
27
63
40
8
220
220
55
36
80
50
10
220/380
220
66
45
100
63