background image

 

1

 

SYSTEMS 

1.1

 

BRIEF INTRODUCTION 

DSP series UPS are mainly applied to computers, data center, administration 

center of networks, precision instruments ect. providing high reliable AC 

uninterruptible power supply. 

The UPS, equipped with dual-conversion  design with output isolation 

transformer and advanced complete digital control technology, keep on providing the 

load with clean uninterruptible power with stable voltage and frequency when the 

mains off. 

 

1.2

 

SYSTEMS CONFIGURATION 

INV

PFC

REC

FITER

Bypass input

AC input

Battery

 

DSP series UPS is composed of input & output switches, input & output EMI 

filter, rectifier, inverter, output transformer, static switches, battery, maintenance 

bypss switch ect. 

The main circuit of input power through air breaker input, and get into rectifier 

unit by input EMI filter.The rectifier transfer AC power to DC power then get into 

PFC circuit to improve UPS input power factor.The partial circuits adopt time delay 

soft-start and PFC control technology improving system’

s impact resistance and input 

power factor and greatly decreasing the harmonic pollution when UPS come back to 

energy grids and making UPS use power much better.   

Battery connection gets through the switch and contactor, and boost upto DC Bus 

Summary of Contents for 38810

Page 1: ...1 User s Manual UNINTERRUPTIBLE POWER SUPPLY R ...

Page 2: ...ng for maintenance Do not touch the electrolyte flooded from the damaged battery as the electrolyte is corrosive The unit battery should keep same brand and same type Forbid mixed using different battery from different manufacturers The unit is class A product it may cause radio interference on environment Do not try to change the unit configuration it may affect the unit performance Operate the u...

Page 3: ...troduction of hot standby in series connection 14 2 8 1 Make the slave UPS connected to the master UPS s input bypass then become a hot standby system See sketch map2 4 14 2 8 2 Cable connection of hot standby 15 2 8 3 work pinciple of hot standby 15 2 9 Inspection of installation 16 2 9 1 Inspection of UPS 16 2 9 2 Electric inspection 16 3 ON OFF OPERATION 16 3 1 Preparation before switching on t...

Page 4: ...ontact instructions 23 5 5 SNMP instructions 23 5 6 EPO interface 24 6 Daily Maintenance 24 6 1 Battery use and maintenance 24 6 2 UPS maintenance 24 6 3 Safe Step Maintenance 24 6 4 Troubleshoot 25 6 5 package shippment and storage 26 6 5 1 package 26 6 5 2 shippment 26 6 5 3 storage 26 ...

Page 5: ...Battery DSP series UPS is composed of input output switches input output EMI filter rectifier inverter output transformer static switches battery maintenance bypss switch ect The main circuit of input power through air breaker input and get into rectifier unit by input EMI filter The rectifier transfer AC power to DC power then get into PFC circuit to improve UPS input power factor The partial cir...

Page 6: ... logic control ect adopt DSP digital signal manager which has high precision fast speed easy circuit and high reliability The systems has the following working modes 1 3 Working Mode l Normal working mode INV PFC REC FITER Bypassinput ACinput Battery Figure1 1 Normal working mode Figure 1 1 when the AC is normal the AC will pass the UPS through rectifier and inverter and the UPS will output pure a...

Page 7: ...e short circuit or failure UPS will turn off the inverter automactially and turn on the bypass static switch and then the bypass will supply the power to load At the same time UPS is uable to provide uninterruptible power to the load and the power is just supplied by AC from the bypass l Maintenance working mode INV PFC REC FITER Battery ACinput Bypassinput Figure1 4 Maintenance working mode Figur...

Page 8: ...TCP IP protocol 5 Big LCD display 6 Perfect protection UPS has input low over voltage protection output low over voltage protection overload protection short circuit protection overheat protection ECO protection surge protection ect 7 Cold start and AC start functin When there is no AC UPS can start by the battery set or when there is no battery UPS can start by AC when AC returns UPS starts autom...

Page 9: ...or 10min 125 150 load for 1min 150 load for 1s AC ouput Transfer time AC battery zero transfer bypass inverter zero transfer AC abnormal Interval for 4S beep for 1S after 1min beep stops automatically Battery low voltage Interval for 1S beep for 1S beep continously Overload alarm Interval for 4S beep for 2S beep continously Alatm Failure alarm Continuous beeps display LED LCD Protection function O...

Page 10: ... Placement The provided AC power capacity must meet the requirement of UPS normal working Please use unique air switch for input and output connection Install UPS as close as possible to the utility power outlet The floor board of UPS installed place should be good enough to support the weight of UPS Any dangerous installation is forbidden No storage of flammable explosive and other dangerous good...

Page 11: ...d UPS Capacity the voltage of input and output frequency the phase of input and output battery voltage 2 4 Dimension of structure and instruction ENTER ON OFF SCREEN E S C LINE BYPASS BAT INV F A U L T Figure2 1 Drawing of structure As the UPS has the ventilation holes in the front side back side right side and left side as long as the bottom please make sure there is enough space so that the air ...

Page 12: ...itable wires or air switch will easily bring dangers The principle of selection are 3 5A mm2 for middle and small size UPS 2 5 3A mm2 for big power UPS Meantime we should consider to control the max voltage drop no more than 3V There have input neutral wire for bypass and output neutral wire for UPS power in the UPS midline system For three phases in and single phase out UPS the cross sectional ar...

Page 13: ...0 16 6 6 8 16 By pas s 6 6 8 10 10 16 25 35 Output 6 6 8 10 10 16 25 35 Battery 6 8 10 10 10 16 25 35 Neutral 6 8 10 16 10 16 25 35 Earthin g 6 6 6 6 6 6 6 8 Note The real wires should be no smaller than the figures in above table 2 6 Instruction of input and output terminal The terminal is on the rear panel see below figure for details on terminal plate N L JP2 JP1 N L E E INPUT OUTPUT BYPASS PE ...

Page 14: ...ust be short connected with 10mm2 wire when operate a single UPS 2 Anode cathode of battery and live wire neutral wire cannot be connected in reverse 2 8 Installation introduction of hot standby in series connection 2 8 1 Make the slave UPS connected to the master UPS s input bypass then become a hot standby system See sketch map2 7 Master UPS AC input Load INV REC Bypass UPS Slave Figure2 7 AC IN...

Page 15: ...ect the neutral line earth of the mater and slave in parallel and make the output line of slave connected to input of the master JP2 JP2 and ouput neutral and earth in prallel and loads will be at the ouput of the master 2 8 3 work pinciple of hot standby Normal work mode Master UPS Slave UPS Load AC input REC REC INV INV Bypass Bypass Load Figure2 10 Nomal work flow Figure 2 10 stands for system ...

Page 16: ...e Whether there is sundries around the UPS body or around it 2 9 2 Electric inspection After UPS switching finished plz inspect following items The input and output switching is ok and the in and out terminals are canonical Make sure the input and ouput connected cable steady phase series correct and mark complete Make sure battery cable connection fastened polarity normal and battery setted stead...

Page 17: ... on output switch 3 3 Steps of switching off single UPS 1 Shut off output switch 2 Shut off the UPS Long press ON OFF button above 1second 3 Shut off battery switch 4 Shut off bypass 5 Shut off AC input switch 3 4 Hot standby system starting steps First start the slave UPS the Standby UPS Start steps are the same as turn on single UPS Then turn the master UPS Start steps are the same as turn on si...

Page 18: ... on the bypass switch input switch battery switch and bypass light will be on 6 Shut off manual maintenance switch 7 Switch on the inverter Long press ON OFF button above 1s and 10s later UPS goes into normal working status 4 Operation of front panel 4 1 The structure function of front panel 2 3 7 8 9 10 6 5 4 1 FAULT INV BAT BYPASS LINE ESC SCREEN ON OFF ENTER 1 LCD display screen Display the wor...

Page 19: ... points or the setting of parameter 10 ON OFF Press it over 1 second the UPS will start or turn off 4 2 The instruction os setting Choose the language When UPS is in Sleep model press ENTER to enter the main page press Screen and choose System setting then press Enter to choose Languanse setting after chose the Language that you need press ENTER to confirm 4 3 Display content 1 Turn on the A C inp...

Page 20: ...enter start model 3 10 seconds later UPS will transfer to Inverter output the sleep model becames main power model 4 Press Enter to enter Function Menu 5 Select parameter setting and press Enter to check parameters O P VOLT 000 V O P FREQ 00 0 HZ O P LOAD 000 MODE STANDBY UPS UPS TO ON IN PROGRESS PLEASE WAIT STATUS SEAUP MODEL INFO OUTPUT DATA INPUT DATA BATTERY DATA DC LINK DATA ...

Page 21: ...odel info and press Enter 4 10KVA single phase UPS 2 10 30KVVA three phase input and single phase output 8 Or you may select battery parameter and press Enter to check the battery status WATT 0 0 0 0 0W VA 0 0 0 0 0VA VOLTAGE 0 0 0 V FREQ 0 0 0HZ LOAD 000 CURRENT 000 A LINE VOLT 0 0 0 V FREQ 0 0 0 HZ R N 0 0 0 V S N 0 0 0 V T N 0 0 0 V ...

Page 22: ...he UPS information 11 Press the ON OFF for more than 1 second the UPS will be turned off LCD will display as below 5 Communication Interface UPS supplies many communication interface methods including RS232 and BAT VOLT 0 0 0 V BUS VOLT 0 0 0 V LOGO Brand TYPE 1 IN 1 OUTPUT CAPACITY 10KVA MODEL 8810 ON LINE UPS UPS TO OFF IN PROGRESS PLEASE WAIT ...

Page 23: ...s intercommunication to complete remote monintoring Output data cable adopts twisted pair cable There are three cables A 485 B 485 and GND respectively 5 3 USBinstructions UPS also supplies USB interface It adopts stochastic USB communication It completes real time monitoring and management without RS232 5 4 Dry Contact instructions Inactive voltage and current is 120VAC 1A or 24VDC 1A such as Sig...

Page 24: ...please note that use same brand and capacity to avoide confused 8 No stopping power for a long time user should discharge artifically for 4 to 6 months User stops discharging within 50 capacity 9 Its current is small inadvisably to protect deep discharge and damage battery 6 2 UPS maintenance 1 Please check if input and output connection is ok or not for a certain period 2 Please check if UPS work...

Page 25: ...en turn on UPS Power supply board failed Contact technician man repair Battery switch don t turn on or failed Check power supply switch Line is failed and No output Low battery to supply Contact technician man testing UPS don t have communitcation Communicate softeware wrongly set and data cable has failure Reset and change data cable UPS don t start up in line and UPS works normally in battery Ch...

Page 26: ...n sign Don t put UPS to drench solarization Don t also put UPS with flammability Explodition and causticity goods together when UPS is in transit When UPS download you use special equipment to avoid bump concussing and damagement 6 5 3 storage UPS should put in dry environment to prevent drenching and solarization The temperature of storage is within 0 40 And the humidity of storage is within 20 9...