62
MessengerBLE
User Guide
Parameters for Digital Channel Configuration
(channel numbers 1-50 are pre-defined digital channels)
Parameter
Code
Reference
Description
Default
Output
State on
Alarm
Range 0-3
0 = de-activate (open)
1 = activate (close)
2 = undefined
3 = static (do not change the current
state)
6
Normal
(Idle) State
State of input when condition being
monitored is normal.
Normally
Open [0]
0 – open or > 3.0V
1 – closed to ground
7
Modbus
slave bit
packed
position
(bitpos)
Read Only
8
Duration
Limit
A limit on the accumulated time that
this input is not normal.
-1
Range -1 to 9999999 seconds
-1 disables limit
9
Starts Limit A limit on the number of times the
input transitioned to not normal.
-1
Range -1 to 9999999 counts
-1 disables limit