IOM-BQ
2
a. Recommended installation is with the spring cham ber
directed upwards.
b. No corrosive
fl
uid should be utilized for spring cham-
ber loading.
c. System operation should ensure that loading pres-
sure (P
LOAD
) not exceed inlet pressure (P
1
); in ter nal
diaphragm damage may occur if this op er a tion al
mode occurs.
11. Regulators are not to be direct buried underground.
12. For insulated piping systems, recommendation is to not
insulate regulator.
13. Spring Chamber Vent Tap - Option -25: Pipe spring
chamber vent opening to remote location. Orient so as
not to take on rainwater.
10a. Basic Regulator - (Refer to Figure 1): Regulator may
be rotated around the pipe axis 360°. Recommended
positions are with the spring chamber vertical upwards,
or horizontal. Orient such that the spring chamber vent
hole does not collect rainwater or debris.
10b. Cryogenic Regulator - Option -5 or -36 (Figure 2):
a. Recommended installation is with spring cham ber
hang ing directly below the body in a ver ti cal down-
wards orientation. Allow water to drain; i.e. melting
frost, rain water.
b. Recommend inert purge gas to spring cham
ber
through vent hole and out drain hole.
10c. Differential Regulator - Option -1+6 (Refer to Figure 3).
7. Slowly open the outlet (downstream) block valve ob-
serv ing the inlet (upstream) pressure gauge. De ter mine
if the regulator is
fl
owing. If not, slowly rotate the regula-
tor adjusting screw counterclockwise (CCW) until
fl
ow
begins.
8. Continue to slowly open the outlet (downstream) block
valve until fully open.
9. Observing the inlet (upstream) pressure gauge, rotate
the adjusting screw clockwise (CW) slowly until the inlet
pressure begins to rise. Rotate CW until the desired
setpoint is reached.
10. Continue to slowly open the inlet (upstream) block valve.
If the inlet (upstream) pressure exceeds the desired
setpoint pressure, rotate the adjusting screw (CCW)
until the pressure decreases.
11. When
fl
ow is established steady enough that both the
outlet and inlet block valves are fully open, begin to
slowly close the bypass valve if installed.
12. Develop system
fl
ow to a level near its ex pect ed normal
rate, and reset the regulator setpoint by turning the
adjusting screw CW to increase inlet pressure, or CCW
to reduce inlet pressure.
13. Reduce system
fl
ow to a minimum level and observe
setpoint. Inlet pressure will rise from the setpoint of Step
9. (Ensure that this rise does not exceed the stated upper
limit of the range spring by greater than 50% i.e. 30-80
psig (2.07 - 5.52 Barg) range spring, at maximum
fl
ow
the inlet pressure should not exceed 1.5 x 80 (5.6 Barg)
or 120 psig (8.3 Barg). If it does, consult factory.)
14. Increase
fl
ow to maximum level if possible. Inlet (up-
stream or P
1
) pressure should rise. Readjust setpoint
as necessary at the normal
fl
ow rate.
IV. STARTUP
* NOTE:
Systems sequencing operations at startup, normal opera-
tion, failure mode(s), and shutdown must assure that the pressure
(P
Load
) on the spring chamber does not exceed the pressure regis-
tering on the wetted side of the diaphragm. Should this "pressure
reversal" occur, particularly to metal diaphragms, the diaphragm
may be permanently damaged and cause improper operation.
P
1
> P
Load
Pressure reversal is normally caused by the inlet pressure
to a regulator being interrupted (automatically or manually).
1. Ensure that the proper range spring is indicated to be
within the regulator by inspection of the unit's name plate.
Apply setpoint pressures that are only within the stated
range.
2.
When stating direction of rotation of the adjustment screw,
the view is with respect to looking down towards the
adjusting screw or its normal location.
3.
Start with the block valves closed. A bypass valve may be
used to maintain inlet pressure in the upstream system
without changing the following steps.
4. Remove closing cap, if installed. Relax the range spring
by turning the adjusting screw counterclockwise (CCW)
a minimum of three (3) full revolutions. This reduces the
inlet (upstream) pres sure setpoint.
5. If it is a “hot” piping system, and equipped with a by-
pass valve, slowly open the bypass valve to pre-heat
the system piping and to allow slow expansion of the
piping. Ensure proper steam trap operation if installed.
Closely monitor inlet (upstream) pressure, via gauge, to
ensure not over-pressurizing. NOTE: If no bypass valve
is installed, extra caution should be used in starting up
a cold system; i.e. do everything slowly.
6. Crack open the inlet (upstream) block valve.
III. PRINCIPLE OF OPERATION
1. Movement occurs as pressure variations register on
the diaphragm. The registering pressure is the inlet,
P
1
or upstream pressure. The range spring opposes
di a phragm movement. As inlet pressure drops, the range
spring pushes the diaphragm down, closing the port;
as inlet pressure increases, the di a phragm pushes up
and the port opens.
2. A
com
plete diaphragm failure will cause the outlet
process
fl
uid to mix with the loading
fl
uid.
SECTION III
SECTION IV