The regulation of the CO
2
control is carried out in the frequency converter (three-phase fans) or the voltage converter (single-phase fans) being, in
the case of inverter frequency, a percentage value of the reading range of the sensor, and if the inverter of voltage the value of the desired concen-
tration of carbon dioxide (ppm).
For variable frequency, the adjustment is made as follows:
MENÚ [FUn-]
SUBMENU [PI]
CATEGORY [rPI]
The value of the intended regulation being here imposed.
ACCESSORIES - CO
2
CONTROL
For the voltage variators the regulation is carried out in the following way:
- Press the “A / M” button continuously.
- In the settings menu, set the value of the desired regulation (ppm).
Feeding
230 VAC±10%-50Hz
Maximum sensor range (SR)*
0-10000 Pa
Adjustment points (SP mín/SP máx)
10-90% SR
Proportional range **
5-75% SR
Rules
Low voltage directive 2014/35/EU
EMC directive 2014/30/EU
WEEE directive 2012/19/EU
RoHs directive 2011/65/EU
Simple milling:
Manual mode
Continuous milling:
Installation menu
Adjustment regulator