background image

times in quick succession as before. The LED will stop blinking when sound is restored to its 
previous setting. 

ADJUST TIMING (OPTIONAL) 

The default timing for the CT-A1 is set at the control unit (see “Adjusting Sounder (Annunciator) 

Time” on page 2). However, if a longer sounding time is desired for individual CT-A1’s, it can be 
lengthened by turning the pot on the sounder’s circuit board counter-clockwise (CCW). 

CONNECTING CT-A1 SOUNDER TO CT-2B CONTROL UNIT 

See Figure 4. 
Connect wires to CT-A1 first, then to the CT-2B. 

 

At CT-A1, connect a wire to terminal “V.” At 
CT-2B, test resistance as noted above and 
connect to terminal 3. 

 

At CT-A1, connect another wire to terminal “G.”  
At CT-2B, test resistance and connect this wire 
to terminal 8.  

 

At CT-A1, connect a third wire to terminal “S” (for steady tone) or “P1” (for fast pulsating tone) or 
“P2” (for slow pulsating tone). At CT-2B, test resistance and connect this wire to terminal 9. 

NOTE: The three extra functional buttons on the CT-A1 (“ON”, “RESET”, “EXIT”) are non-functional 
when used with the CT-2B. They should be ignored. 

For using CT-A1 with a two or three-driveway system, see manual that came with CT-A1. 

INSTALLING CT-11 SOUNDER 

See Figure 1 on page 1. Please read the instructions in the introduction. First make the 

connections at the CT-11 plate and then to the control unit as follows: 

Connect one colored wire to the terminal marked “−”. At the control unit, test the resistance as 

noted above. Then proceed to connect this wire to terminal 8. 

Connect another colored wire to the terminal marked “+”. At the control unit, test the resistance as 

noted above. Then proceed to connect this wire to terminal 9. 

INSTALLING AA-1 SOUNDER 

See Figure 1 on page 1. Connect the RED lead to the terminal marked SON on the sounder. 

Connect the BLACK lead to GND on the sounder. At the control unit, test the resistance RED to 
BLACK as noted above. If resistance proves correct, at the control unit connect the RED lead to 
terminal No. 9. Twist the BLACK lead to the SHIELD wire and connect to terminal No. 8. 

F

IELD

 T

ROUBLESHOOTING

 

Figure 4 

Cartell does not provide circuit diagrams or service manuals. However, we try very hard to provide 

fast repair service and 

(800) 878-7829

 phone number by which technical support may be reached. 

Before calling 

us

, there are some simple procedures you can follow. The vast majority of all 

service problems result from a fault with the control unit and not from the probe. 

Disconnect the probe wires from the control unit and perform the resistance tests listed in "CT-6 

Probe and Wire Check-Out” on page 3. The resistance tests will determine the health of the probe 
and wire.  

If the probe reading indicates a bad probe, do not immediately dig it up. Rather, if there is a splice 

in the line, locate it and cut the wire on the probe side of the splice. Then retest it. If the probe still 
tests bad, go to the sensor probe itself and cut the wire one foot from the probe and retest it. If the 

www.GateOpenerSafety.com  |  (800) 878-7829  |  [email protected]

Summary of Contents for DRIVEGUARD

Page 1: ...ALLATION OPERATION MANUAL Manufactured by THIS MANUAL COVERS THE FOLLOWING SYSTEMS DRIVEGUARDTM DRIVEGUARD INTEGRATORTM PIONEERTM Free Exit System TM www GateOpenerSafety com 800 878 7829 Sales GateOp...

Page 2: ...ng With a Security or Home Automation System 3 CT 6 Probe and Wire Check out 3 System and Probe Don ts 3 Location of CT 6 Probe 4 Installing CT 6 Probe and Cable 4 Connecting CT 6 Probe to Control Uni...

Page 3: ...ONTROL UNIT Install the control unit in a dry weatherproof building away from heavy electrical motors radio transmitters main power service or any equipment that may introduce electrical or R F noise...

Page 4: ...1 This function controls the amount of time the customer desires the sounder s to stay on It may be adjusted to stay on anywhere from 1 2 to 15 seconds To adjust use the potentiometer A CW to increase...

Page 5: ...manual for resistor size If your H A contacts are normally open use terminals 6 7 on the CT 2B and place a resistor between the terminals in series see your H A manual for resistor size CT 6 PROBE AND...

Page 6: ...from traffic respectively This is made possible by adjusting the probe s sensitivity See Adjusting Probe Sensitivity on page 2 Stationary steel near the probe but not over the probe will not affect it...

Page 7: ...ber casing Therefore make sure you lubricate it when pulling it through conduit or PVC pipe Also the polyurethane coating on the probe cable demands that extreme care be taken when unrolling it To unr...

Page 8: ...is connected to the control unit CT A1 SOUNDER FEATURES AND INSTALLATION REPLACES FC 9 CT 8 CT 8A SOUNDERS THREE TONES The CT A1 allows three tones steady slow pulse fast pulse It is suggested the in...

Page 9: ...resistance as noted above Then proceed to connect this wire to terminal 8 Connect another colored wire to the terminal marked At the control unit test the resistance as noted above Then proceed to co...

Page 10: ...sure it is polyurethane coated or it will not splice Improper cable splices will cause false alarms and failures For proper splicing follow the instructions below Two items are necessary when splicin...

Page 11: ...rization R M A number TECHNICAL SPECIFICATIONS CONTROL UNIT TECHNICAL SPECIFICATIONS SENSOR PROBE 9 POWER REQUIRED 8 31 VAC 10 41 VDC Issue 4 12 VAC or 11 18 VDC Issue 3 STANDBY CURRENT Under 1 mA boa...

Reviews: