Enthalpy switch/receiver and Enthalpy sensor
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
65
To wire and mount the switch/sensor
For Outdoor Enthalpy Control
1
To mount the enthalpy switch/receiver, insert 2 field-supplied 8 x 3/4-in. TEK screws through its side holes.
2
Remove the 4 screws holding the cover on, then remove cover.
3
Set the
M1
to
M3
jumper to
M2
. Leave the other jumper on
Off
.
4
Replace the cover and the 4 screws.
5
Connect the
GND
and
24 Vac
terminals on the enthalpy switch/receiver to the controller's power terminals.
6
Connect the
HI
or
LOW
terminals on the enthalpy switch/receiver to the controller's J2-6 input.
Downloaded from