![Carrier ZS Plus Installation Manual Download Page 26](http://html.mh-extra.com/html/carrier/zs-plus/zs-plus_installation-manual_2560240026.webp)
SPT Sensors
Carrier Sensors
CARRIER CORPORATION ©2021
Installation Guide
All rights reserved
22
To communicate through the local access port
You can connect to the Local Access port of the ZS Sensor to perform test and balance or to make changes to any
device on the network.
PREREQUISITES
•
A computer with a USB port
•
A USB Link (Part #USB-L)
CAUTION
If multiple controllers share power but polarity was not maintained when they were wired, the
difference between the controller's ground and the computer's AC power ground could damage the USB Link and
the controller. If you are not sure of the wiring polarity, use a USB isolator between the computer and the USB
Link. Purchase a USB isolator online from a third-party manufacturer.
Connect the USB Link to the computer and to the ZS Sensor's local access port.
USB Link
Connect to
Local Access port
1 2 ft
Connect to
U SB port
7 3/4 in.
NOTE
If using a USB isolator, plug the isolator into your computer's USB port, and then plug the USB Link cable
into the isolator.