ZONECC3Z(AC/HP)01

3---Zone Control System

Quick Reference Guide

ZONECC3ZAC01

1 Heat / 1 Cool

ZONECC3ZHP01

3 Heat / 2 Cool HP

INTRODUCTION

The Carrier 3--Zone Control system brings the possibility of total

comfort control to the occupants by providing the right amount of
heating or cooling for up to 3 distinct spaces or zones within a

home or business. Each zone has independent temperature settings

controlled by a conventional thermostat or Wi--Fi

r

based

thermostats and up to 5 dampers per zone.
The Quick Reference Guide will provide a simplified description
on installing the 3--Zone Control System. Please reference the

Installation and Start- Up Instructions

included in the 3--Zone

Controller packaging for the complete design and installation
information on the 3--Zone System.

PRODUCT FEATURES AND BENEFITS

S

Duct Temperature Optimizer -- Offers maximum equipment
protection to help ensure long life.

S

Wi--Fi

r

Thermostat compatibility -- Matches the right thermostat

to the homeowner’s comfort and lifestyle.

S

Diagnostic LEDs -- Intelligent system diagnostics to let
homeowners know if there is a problem with their system.

S

Emergency Heat Switch -- Allows manual override for
emergency heat strip operation when utilizing a heat pump.

S

Max Cycle Rate -- Allows 4 equipment cycles per hr (cph)
providing maximum equipment protection.

S

Selection Jumpers -- Designed for easy configuration

S

Additional Options

S

Timeguard override

S

Compressor protection

S

Modulating damper control in emergency situations

S

Damper fuse protection

S

High and low temperature limits

S

Auto changeover from any zone

S

RH and RC for voltage isolation

S

Bypass setup routine

S

Staging time for energy savings

S

Automatic checkout with installer mode

S

Override zoning switch

S

Timer override for serviceability

COMPONENTS NEEDED

3--Zone Control Panel

S

Separate transformer is not needed to provide power

S

Designed so that wires can enter from behind, above, or below

S

Each system controller also includes a duct temperature sensor

24v or Wi--Fi

r

Thermostats

S

Advanced energy savings algorithms

S

Remote access

TSTWHA01

Côr 7C

Thermostat

TP--WEM01--A

Côr Thermostat

Dampers (8--in. -- 24--in.)

S

Up to five dampers may be used in each zone by electrically
connecting them in parallel

S

By--pass damper available to prevent static pressure buildup

AIRFLO

W

AIRFLO

W

CLS  COM  OPN

CLS  COM  OPN

A05252

A05251

Rectangular

Damper

Round Damper

By--Pass

Leaving Air Temperature

(LAT) Sensor

Slip--In Damper

Fig. 1 -- Damper Types

NOTE

: Thermostats and Dampers are sold separately.

Wi---Fi

R

is a registered trademark of the Wi---Fi Alliance Corporation

Summary of Contents for ZONECC3ZAC01

Page 1: ...peration when utilizing a heat pump S Max Cycle Rate Allows 4 equipment cycles per hr cph providing maximum equipment protection S Selection Jumpers Designed for easy configuration S Additional Options S Timeguard override S Compressor protection S Modulating damper control in emergency situations S Damper fuse protection S High and low temperature limits S Auto changeover from any zone S RH and R...

Page 2: ...tuator required 3 conductors S The connection to thermostat and equipment furnace or fan coil could require as many as 8 conductors for a multi state installation S The Leaving Air Temperature LAT and Heat Pump Temperature HPT used with heat pumps only sensors require 2 conductors each S Cables with excess conductors are acceptable Step 1 Mounting the Carrier 3 Zone System The Carrier 3 Zone Syste...

Page 3: ...3 Thermostat Wiring Example Zone 1 Zone 2 Fig 3 Wiring Diagram for Installation of Thermostats Fig 4 Installing Dampers ...

Page 4: ...g to detect a heating overload condition at the coil with a shutdown temperature of 115_F It can be installed through the wall of the fan coil or may be located entirely inside the fan coil near the blower inlet being careful that it does not interfere with the blower wheel If the HPT sensor is not used the 10K ohm resistor attached to the 2 HPT terminals on the board must be left in place NOTE ZO...

Page 5: ...T energized with G OFF W energized with G ON 7 Sets Leaving air Temperature LAT limit temperature HP 2 Stage control only 145_F OFF OFF 160_F ON 175_F ON 8 130_F ON OFF 9 Designated Zoning Controller connection to heat pump HP or an air conditioner AC 1 or 2 Speed HP 1 Stage Aux Heat OFF 1 or 2 Speed AC 1 or 2 Stage Heat1 ON 1 Speed HP 1 Stage Aux Heat2 OFF 10 Designates the type of thermostat use...

Page 6: ...AT EQIUPMENT POWER FURNACE OR FAN COIL AIR CONDITIONER COOL LO HEAT FAN R C Y Y2 G Rz C HI HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 ON SWITCH 10 ON R C Y1 G W1 Y2 W2 O R C Y G W2 C Y A04197 HP 2S 3 Zone Control AC Stat 1 Stg AC with 1 or 2 Stg Heat H P 2S 3 ZONE CONTROL ZONE 1 INPUT ZONE 1 AC TSTAT EQIUPMENT POWER FAN COIL HEAT PUMP COOL HP HEAT FAN R C Y Y2 G Rz C AUX HEAT R C Y1 G W1 Y2 W2 O SWITCH 9 O...

Reviews: