Refrigerant Piping

• Piping kit used for the conventional refrigerant cannot be used.

• Use copper pipe with 0.8 mm or more thickness for Ø 9,52

mm.

• Use copper pipe with 1.0 mm or more thickness for Ø 15,87 mm.

• Flare nut and flare works are also different from those of the

conventional refrigerant.
Take out the flare nut attached to the main unit of the air
conditioner, and use it.

Cooling (2)

Maximum conditions

outdoor temperature 43

°

C

indoor temperature 32

°

C d.b.; 23

°

C w.b.

Minimum conditions

outdoor temperature -5

°

C

indoor temperature 21

°

C d.b.; 15

°

C w.b.

Heating (2)

Maximum conditions

outdoor temperature 24

°

C d.b.; 18

°

C w.b.

indoor temperature 27

°

C d.b.

Minimum conditions

outdoor temperature –15

°

C d.b.

Mains power supply

Nominal single-phase voltage

220

÷

240V ~ 50Hz

Operating voltage limits

min. 198V – max. 264V

Table IV: Operating limits 

(1)

Notes:

1. Data referred to the outdoor unit only.
2. According to prEN14511.

d.b. - dry bulb;

w.b. - wet bulb

WARNING:
During heat pump operation unit will undergo several defrost cycles to
eliminate ice that might possibly collect on the outdoor unit in very low
ambient temperatures.
In these cycles, fan speed will automatically reduce and cannot be
varied until defrost cycle is completed.

NOTES: Caution at addition of refrigerant

(1)

When the total length of refrigerant pipe exceeds 20m, add 40g/m. The pipe total maximum length is  50 m. (Max. amount of additional refrigerant is
1200g.). Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor..

Table III: Length of refrigerant

Length of refrigerant pipe connected
to indoor/outdoor units.

Refrigerant addition

.

20 m o shorter: for all units

Do not add refrigerant at installation site

(1)

 from 20 m to 50 m

Add 40 g of refrigerant for every meter of pipe beyond 20 m

Air purge

• For air purge, use a vacuum pump.

• Do not use refrigerant charged in the outdoor unit for air purge.

(The refrigerant for air purge is not contained in the outdoor unit.)

Selection of installation

Electrical cabling

• Be sure to fix the power cables and indoor/outdoor connecting

cables with clamps so that they do not contact with the cabinet,
etc.

Summary of Contents for XPOWER 38VYX110

Page 1: ...38VYX110 38VYX130 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 INSTALLATION MANUAL...

Page 2: ...rate with R 410A R 410A refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top R...

Page 3: ...other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may cau...

Page 4: ...nit only 2 According to prEN14511 d b dry bulb w b wet bulb WARNING During heat pump operation unit will undergo several defrost cycles to eliminate ice that might possibly collect on the outdoor unit...

Page 5: ...es not block a passage When the outdoor unit is installed in an elevated position be sure to secure its feet There must be sufficient space for carrying in the unit A place where the drain water does...

Page 6: ...cannot be tightened with necessary tightening torque On the contrary use a single spanner to loosen or tighten the flare nut of the valve at liquid side REQUIREMENT 1 Do not put the spanner on the cap...

Page 7: ...e lower than the height of the outdoor unit The height of the obstacle should be lower than the height of the outdoor unit 150 or more 300 or more 300 or more 300 or more 200 or more 150 or more 500 o...

Page 8: ...r more 300 or more 1000 or more Open the upper side and both right and left sides The height of obstacle at both front and rear side should be lower than the height of the outdoor unit Serial installa...

Page 9: ...local procure CAUTION IMPORTANT FOR POINTS BELOW FOR PIPING WORK 1 Keep dust and moisture away from inside the connecting pipes 2 Tightly connect the connection between pipes and the unit 3 Evacuate t...

Page 10: ...cmHg 1 Close handle Low completely Turn OFF the vacuum pump Leave the vacuum pump as it is for 1 or 2 minutes and check the indicator of the compound pressure gauge does not return Open fully the valv...

Page 11: ...use a wire jointed to another on the way Use wires long enough to cover the entire length Evacuating Open the valve stem or the handle until it strikes the stopper It is unnecessary to apply further...

Page 12: ...D801 O Yellow Outdoor air temperature sensor error TO D802 O Yellow Outdoor motorised fan error DC D803 O Yellow Communication error between IPDU Abnormal stop High pressure release operation Flashin...

Page 13: ...other refrigerant from being charged each port diameter is changed In order to increase pressure resisting strength Charge hose x hose materials and port size are changed to 1 2 UNF 20 threads per in...

Page 14: ...38VYX 110 130 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2003 Printed in Japan...

Reviews: