background image

GB - 2

38VYX110/38VYX130 

General information

Precautions for safety

The unit must be installed according to the national plant-
engineering standards.
• Read this “PRECAUTIONS FOR SAFETY” carefully before

Installation.

• The precautions described below include the important items

regarding safety.  Observe them without fail.

• After the installation work, perform a trial operation to check for

any problem.
Follow the Owner’s Manual to explain how to use and maintain the
unit to the customer.

• Turn off the main power supply switch (or breaker) before the unit

maintenance.

• Ask the customer to keep the Installation Manual together with the

Owner’s Manual.

CAUTION:

• This air conditioner adopts the new HFC refrigerant (R410A)

which does not destroy ozone layer.
The characteristics of R410A refrigerant are ; easy to absorb
water, oxidizing membrane or oil, and its pressure is approx. 1.6
times higher than that of refrigerant R22.
Accompanied with the new refrigerant, refrigerating oil has also
been changed.
Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil,
the sizes of connecting sections of charging port of the main unit
and installation tools are charged from those for the conventional
refrigerant. Accordingly the exclusive tools are required for the
new refrigerant (R410A).

• Connect indoor and outdoor units with field-supplied copper pipes

by means of flare connections. Use insulated seamless
refrigeration grade pipe only, (Cu DHP type according to
ISO1337), degreased and deoxidized, suitable for operating
pressures of at least 4200 kPa and for burst pressure of at least
20700 kPa. Under no circumstances must sanitary type copper
pipe be used.
Moreover, do not use the existing piping because there are
problems with pressure-resistance force and impurity in it.

• Check that the impedance of the mains power supply is in

conformance with the unit power input indicated in the
electric data (EN 61000-3-11).

• This unit complies with low-voltage (EEC/73/23) and electro-

magnetic compatibility (EEC/89/336) directives.

• This appliance must be connected to the main power supply by

means of a switch with a contact separation of at least 3 mm.
The installation fuse (25A D type 

 ) must be used for

the power supply line of this conditioner.

WARNING:
• Ask an authorized dealer or qualified installation professional to

install/maintain the air conditioner. Inappropriate installation may
result in water leakage, electric shock or fire.

• Turn off the main power supply switch or breaker before attempting

any electrical work. Make sure all power switches are off.  Failure
to do so may cause electric shock.

• Connect the connecting cable correctly. If the connecting cable is

connected in a wrong way, electric parts may be damaged.

• When moving the air conditioner for the installation into another

place, be very careful not to enter any gaseous matter other than
the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure
in the refrigeration cycle becomes abnormally high and it may
cause pipe burst and injuries on persons.

• Do not modify this unit by removing any of the safety guards or by

by-passing any of the safety interlock switches.

• Exposure of unit to water or other moisture before installation may

cause a short-circuit of electrical parts. Do not store it in a wet
basement or expose to rain or water.

• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when

handling parts.

• Perform installation work properly according to the Installation

Manual.
Inappropriate installation may result in water leakage, electric
shock or fire.

• When the air conditioner is installed in a small room, provide

appropriate measures to ensure that the concentration of
refrigerant leakage occurred in the room does not exceed the
critical level.

• Install the air conditioner securely in a location where the base

can sustain the weight adequately.

• Perform the specified installation work to guard against an

earthquake.
If the air conditioner is not installed correctly, accidents may occur
due to the falling unit.

• If refrigerant gas has leaked during the installation work, ventilate

the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious
gas may generate.

• After the installation work, confirm that refrigerant gas does not

leak. If refrigerant gas leaks into the room and flows near a fire
source, such as a cooking range, noxious gas might generate.

• Electrical work must be performed by a qualified electrician in

accordance with the Installation Manual.
Make sure the air conditioner uses an exclusive power supply. An
insufficient power supply capacity or inappropriate installation may
cause fire.

• Use the specified cables for wiring and connect them firmly to

the terminals.
To prevent external forces applied to the terminals from affecting
the terminals.

• Be sure to provide grounding. Do not connect ground wires to gas

pipes, water pipes, lightning rods or ground wires for telephone
cables.

• Conform to the regulations of the local electric company when

wiring the power supply.
Inappropriate grounding may cause electric shock.

• Do not install the air conditioner in a location subject to a risk of

exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may
occur.

Required tools for installation work

-

Philips screw driver

-

Cutter drill (65 mm)

-

Spanner

-

Pipe cutter

-

Cutter

-

Reamer

-

Gas leak detector

-

Meter

-

Thermometer

-

Volt-ohm-milliammeter

-

Electro circuit tester

-

Hexagonal wrench

-

Flare tool

-

Pipe bender

-

Water level

-

Metal saw

R410A (Special requirement)

-

Manometer for pressure measuring
(Charge hose : R410A special requirement)

-

Vacuum pump
(Charge hose : R410A special requirement)

-

Torque wrench:

• 1/4 (17 mm) 16 N•m (1,6 kgf•m)
• 3/8 (22 mm) 42 N•m (4,2 kgf•m)
• 1/2 (26 mm) 55 N•m (5,5 kgf•m)
• 5/8 (15,9 mm) 120 N•m (12,0 kgf•m)

-

Copper pipe gauge adjusting projection margin

-

Vacuum pump adapter

Summary of Contents for XPOWER 38VYX110

Page 1: ...38VYX110 38VYX130 L L O Y D S R E G I S TER QUALIT Y A S S U R A N C E IS O 900 1 INSTALLATION MANUAL...

Page 2: ...rate with R 410A R 410A refrigerant cylinders are pink R 410A refrigerant cylinders have a dip tube which allows liquid to flow out with the cylinder in a vertical position with the valve at the top R...

Page 3: ...other than the specified refrigerant into the refrigeration cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it may cau...

Page 4: ...nit only 2 According to prEN14511 d b dry bulb w b wet bulb WARNING During heat pump operation unit will undergo several defrost cycles to eliminate ice that might possibly collect on the outdoor unit...

Page 5: ...es not block a passage When the outdoor unit is installed in an elevated position be sure to secure its feet There must be sufficient space for carrying in the unit A place where the drain water does...

Page 6: ...cannot be tightened with necessary tightening torque On the contrary use a single spanner to loosen or tighten the flare nut of the valve at liquid side REQUIREMENT 1 Do not put the spanner on the cap...

Page 7: ...e lower than the height of the outdoor unit The height of the obstacle should be lower than the height of the outdoor unit 150 or more 300 or more 300 or more 300 or more 200 or more 150 or more 500 o...

Page 8: ...r more 300 or more 1000 or more Open the upper side and both right and left sides The height of obstacle at both front and rear side should be lower than the height of the outdoor unit Serial installa...

Page 9: ...local procure CAUTION IMPORTANT FOR POINTS BELOW FOR PIPING WORK 1 Keep dust and moisture away from inside the connecting pipes 2 Tightly connect the connection between pipes and the unit 3 Evacuate t...

Page 10: ...cmHg 1 Close handle Low completely Turn OFF the vacuum pump Leave the vacuum pump as it is for 1 or 2 minutes and check the indicator of the compound pressure gauge does not return Open fully the valv...

Page 11: ...use a wire jointed to another on the way Use wires long enough to cover the entire length Evacuating Open the valve stem or the handle until it strikes the stopper It is unnecessary to apply further...

Page 12: ...D801 O Yellow Outdoor air temperature sensor error TO D802 O Yellow Outdoor motorised fan error DC D803 O Yellow Communication error between IPDU Abnormal stop High pressure release operation Flashin...

Page 13: ...other refrigerant from being charged each port diameter is changed In order to increase pressure resisting strength Charge hose x hose materials and port size are changed to 1 2 UNF 20 threads per in...

Page 14: ...38VYX 110 130 Via R Sanzio 9 20058 Villasanta MI Italy Tel 039 3636 1 The manufacturer reserves the right to change any product specifications without notice November 2003 Printed in Japan...

Reviews: