19
Installing Heat Reclaim Ventilation
Installing air hose joint flange: fix four joint flanges
with bolts.
Installing Heat Recovery Ventilation Device Fix
anchor bolts (M10-M12) in the first place then put
metal suspending rack through anchor
bolts and fix it with spacer and nut.
(Check against residual scraps of vinyl foam and
paper inside fan chest; check air hose inside
through hose holes).
When installed aloft, inverted suspension of the
unit is needed; please take care to fix the unit tight
with long foot bolts.
Connecting air hose: when connecting air hose, remember:
a. Do not connect air hose as shown by diagram on the right
Ex.1: Avoid over-bending, e.g., bend angle above 90°.
Ex.2: Avoid multiple bending.
Ex.3: Avoid reduced hose diameter,
E.g., reduced mid-section diameter prohibited.
Ex.4: Avoid bending close to outlet.
b. Air Hose Minimum Bend Radius:
Dia.100mm Hose: 100mm; Dia.150mm Hose: 150mm; Dia.200mm Hose: 300mm; Dia.250mm Hose: 375mm
c. To prevent air leakage, joint section between flange and air hose shall be wrapped with aluminum foil.
d. To prevent short circuit, indoor air inlet shall be installed as far away from air outlet as possible.
e. Please choose air hoses with specs conforming to unit model.
f. Install two external air hoses with regular
obliquity (not below 1/30) to prevent rain water
from back- flowing. At the same time, heat
insulant shall be available for all three air hoses
(two outdoor and one indoor) lest condensed
water ensues. (Insulant material: glass wool
25mm thick) (Refer to diagram on the right)
g. In case of constant high temperature and
humidity in suspended ceiling, install ventilation
device in ceiling.
h. Soft hose and wind softening hose can
effectively reduce exhaust noises.
Fan strength and operating noise shall be
considered when choosing material. Distributors
of products shall be entrusted to choose
material.
i. Default distance between air outlet EA and air inlet OA shall be two times longer that hose diameter.
j. Do not use bent service lid or dome shield as external shield; otherwise, rain water will directly enter. (Deepened
shield is recommended).
k. Make sure that air hose is at least 1 meter away from shield.
Spacer
Ex.1 Ex.2
Ex.3 Ex.4
Available on the Site
Air Hose Joint Flange
Nut
Air Hose Joint Flange
Hook
Bolts
Double
Nuts
Aluminum Foil
Available
on the Site
Obliquity Over
1/30
Heat Insulant
Air Hose Joint Flange
Available on the Site
Aluminum Foil
Summary of Contents for XCT7 40VH A-7G Series
Page 36: ...The manufacturer reserves the right to change any product specifications without notice...
Page 98: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Page 129: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...
Page 191: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...