14
62--61177--01
7.3.
Operation on STANDBY mode
VERY IMPORTANT
THE UNIT MUST BE SHUT--DOWN BEFORE CONNECTING OR DISCONNECTING THE
STANDBY SUPPLY CABLE !
1. Before starting :
-
On the power network : check that the type of current corresponds to the characteristics of the
unit (see paragraph 7.3.3.).
-
On the unit : connect the unit to the power network.
7.3.1. Starting the unit
2. Start the unit by pressing the ON key (9.). Start--up is time--delayed for 10 seconds.
3. The digital display (1.) of the cab control displays the box temperature.
4. Check the temperature setpoint is correct by pressing the SET key (6.). The setpoint temperature is
highlighted on the digital display.
5. Enter a new setpoint if necessary (see temperature setpoint adjustment 7.5. -- page 16).
In the event of difficulty on start--up, check that :
Network supply is ok.
The control box fuses have not blown (refer to the electric schematic supplied with the unit).
The temperature selected by the cab control has not been affected.
7.3.2. Stoping the unit
1. Press the OFF key (8.).
7.3.3. Standby operation guidelines
For safe, reliable operation in Standby mode, it is important to consider the following guidelines :
a. ALWAYS CHECK
that the unit if OFF (Cab command) before connecting or disconnecting it from the
power source.
b.
The extension cable and fuse used for network connection must comply with the legislation currently appli-
cable on the site of use (minimum H07 RNF CEI 245--4) and with the unit specifications as described in
the table below :