52
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for sec-
ond stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
*With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to satisfy the call for second
stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage mechanical cooling is enabled.
†With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on second stage of mechanical cooling Y2-O after the delay if the call for Y1-I and
Y2-I have not been satisfied.
Table 22 — Dry Bulb Operation with DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
Below CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
24v/On
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
Above CO
2
Set
No
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
24v/On
0v/Off
VENTMIN to
VENTMAX
Closed
ON
ON
HIGH
24v/On
24v/On
VENTMIN to
VENTMAX
Closed
Yes
OFF
OFF
LOW
0v/Off
0v/Off
VENTMIN to
VENTMAX
Closed
ON
OFF
LOW
0v/Off
0v/Off
VENTMIN to
Full-Open
Closed to Full-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
VENTMIN to
Full-Open
Closed to Full-Open
Table 23 — Enthalpy Operation without DCV (CO
2
Sensor) — 2 Speed Fan
DEMAND
CONTROLLED
VENTILATION (DCV)
OUTSIDE AIR
GOOD TO
ECONOMIZE
Y1-I
Y2-I
FAN
SPEED
Y1-O
Y2-O
OCCUPIED
UNOCCUPIED
NO CO
2
SENSOR
NO
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
24v/On
0v/Off
MIN POS
Closed
ON
ON
HIGH
24v/On
24v/On
MIN POS
Closed
YES
OFF
OFF
LOW
0v/Off
0v/Off
MIN POS
Closed
ON
OFF
LOW
0v/Off
0v/Off
MIN POS to Full Open
Closed to Full-Open
ON
ON
HIGH
DELAY*
24v/On
0v/Off†
MIN POS to Full Open
Closed to Full-Open
Summary of Contents for WeatherMaster 50HC04
Page 32: ...32 Fig 63 RTU Open Overlay for Economizer Wiring ...
Page 33: ...33 Fig 64 VFD Overlay for W2770 Controller Wiring ...
Page 86: ...86 Fig C 50HC A07 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 91: ...91 Fig H 50HC D12 PAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 93: ...93 Fig J 50HC A04 A06 PAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 95: ...95 Fig L 50HC A07 PAC Power Diagram 208 230 3 60 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 100: ...100 Fig Q 50HC D11 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 101: ...101 Fig R 50HC D11 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 103: ...103 Fig T 50HC D14 PAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 104: ...104 Fig U 50HC D14 PAC Power Diagram 460 3 60 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 124: ...124 Fig AO PremierLink System A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 125: ...125 Fig AP RTU Open System Control A04 A06 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 126: ...126 Fig AQ PremierLink System A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...
Page 127: ...127 Fig AR RTU Open A07 D14 Wiring Diagram APPENDIX D WIRING DIAGRAMS ...