APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
IAQ_
Economizer Min.Position
0 - 100
%
ECONOMIN
5
IAQ Demand Vent Min.Pos.
0 - 100
%
IAQMINP
0
IAQ Analog Sensor Config
0 - 4
IAQANCFG
0
IAQ 4-20 ma Fan Config
0 - 2
IAQANFAN
0
IAQ Discrete Input Config
0 - 2
IAQINCFG
0
IAQ Disc.In. Fan Config
0 - 2
IAQINFAN
0
OAQ 4-20ma Sensor Config
0 - 2
OAQANCFG
0
IAQ Econo Override Pos.
0 - 100
%
IAQOVPOS
100
Diff.Air Quality LoLimit
0 - 1000
DAQ_LOW
100
Diff. Air Quality HiLimit
100 - 2000
DAQ_HIGH
700
DAQ PPM Fan Off Setpoint
0 - 2000
DAQFNOFF
200
DAQ PPM Fan On Setpoint
0 - 2000
DAQFNON
400
Diff. AQ Responsiveness
–5 - 5
IAQREACT
0
OAQ Lockout Value
0 - 2000
OAQLOCK
0
User determined OAQ
0-5000
OAQ_USER
400
IAQ Low Reference
0 - 5000
IAQREFL
0
IAQ High Reference
0 - 5000
IAQREFH
2000
OAQ Low Reference
0 - 5000
OAQREFL
0
OAQ High Reference
0 - 5000
OAQREFH
2000
IAQ Purge
Yes/No
IAQPURGE
No
IAQ Purge Duration
5-60
min
IAQPTIME
15
IAQ Purge LoTemp Min Pos
0-100
%
IAQPLTMP
10
IAQ Purge HiTemp Min Pos
0-100
%
IAQPHTMP
35
IAQ Purge OAT Lockout
35-70
dF
IAQPNTLO
50
SP__
Static Pres.VFD Control?
No
STATICFG
No
Static Pres.Fan Control?
Yes
STATPFAN
Yes
Static Pressure Sensor
Enable/Disable
SPSENS
Disable
Static Press. Low Range
–10 - 0
SP_LOW
0
Static Press. High Range
0 - 10
SP_HIGH
5
Static Pressure Setpoint
0 - 5
"H2O
SPSP
1.5
VFD Minimum Speed
10 - 50
%
STATPMIN
20
VFD Maximum Speed
50 - 100
%
STATPMAX
100
VFD Fire Speed Override
0 - 100
%
STATPFSO
100
Stat. Pres. Reset Config
0-4 (multi-text strings)
SPRSTCFG
0
SP Reset Ratio ("/dF)
0 - 2.00
SPRRATIO
0.2
SP Reset Limit in iwc(")
0 - 2.00
SPRLIMIT
0.75
SP Reset Econo.Position
0 - 100
%
ECONOSPR
5
Stat.Pres.PID Run Rate
1 - 200
sec
SPIDRATE
2
Static Press. Prop. Gain
0 - 100
STATP_PG
20
Static Pressure Intg. Gain
0 - 50
STATP_IG
2
Static Pressure Derv. Gain
0 - 50
STATP_DG
0
Static Press.System Gain
0 - 50
STATP_SG
1
TRIM
Air Temp Lvg SF Trim
–10 - 10
^F
SAT_TRIM
0
RAT Trim
–10 - 10
^F
RAT_TRIM
0
OAT Trim
–10 - 10
^F
OAT_TRIM
0
SPT Trim
–10 - 10
^F
SPT_TRIM
0
Cir A Sat.Cond.Temp Trim
–30 - 30
^F
SCTATRIM
0
Cir B Sat.Cond.Temp Trim
–30 - 30
^F
SCTBTRIM
0
Suct.Press.Circ.A Trim
–50 - 50
PSI
SPA_TRIM
0
Suct.Press.Circ.B Trim
–50 - 50
PSI
SPB_TRIM
0
Dis.Press.Circ.A Trim
–50 - 50
PSI
DPA_TRIM
0
Dis.Press.Circ.B Trim
–50 - 50
PSI
DPB_TRIM
0
Static Press. Trim (ma)
–2 - 2
SPMATRIM
0
Bldg. Pressure Trim (ma)
–2 - 2
BPMATRIM
0
Summary of Contents for WEATHERMAKER 48AJ020
Page 95: ...95 Fig 13 Typical Main Control Box Wiring Schematic A48 7787 ...
Page 96: ...96 TO NEXT PAGE Fig 14 Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 98: ...98 Fig 15 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 6866 ...
Page 102: ...102 TO NEXT PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown A48 7298 ...
Page 104: ...104 Fig 19 Controls Option Wiring Schematic A48 7810 ...
Page 105: ...105 Fig 20 Small Chassis Component Location Size 020 035 Units A48 7301 ...
Page 106: ...106 Fig 21 Large Chassis Component Locations Size 036 060 Units A48 7302 ...