APPENDIX B — CCN TABLES (cont)
SERVICE-CONFIG TABLES (cont)
TABLE
NAME
RANGE
UNITS
POINT NAME
DEFAULT
DEHU
Dehumidification
Config
0-2
DHSELECT
0
Dehumidification
Sensor
1-2
DHSENSOR
1
Econ disable in DH mode?
Yes/No
DHECONEN
No
Vent Reheat Setpt Select
0-1
DHVHTCFG
0
Vent Reheat RAT offset
0-8
deltaF
DHVRAOFF
0
Vent
Reheat
Setpoint
55-95
dF
DHVHT_SP
70
Dehumidify
Cool
Setpoint
40-55
dF
DHCOOLSP
45
Dehumidify
RH
Setpoint
10-90
%
DHRELHSP
55
DISP
Metric Display
Off/On
DISPUNIT
Off
Language Selection
0-1
LANGUAGE
0
Password Enable
Enable/Disable
PASS_EBL
Enable
Service Password
0000-9999
PASSWORD
1111
Contrast Adjustment
–255 - 255
CNTR_ADJ
0
Brightness Adjustment
–255 - 255
BRTS_ADJ
0
DLVT
Dmd Level Lo Heat On
–1 - 2
^F
DMDLHON
1.5
Dmd Level(+) Hi Heat On
0.5 - 20.0
^F
DMDHHON
0.5
Dmd Level(-) Lo Heat Off
0.5 - 2
^F
DMDLHOFF
1
Dmd Level Lo Cool On
–1 - 2
^F
DMDLCON
1.5
Dmd Level(+) Hi Cool On
0.5 - 20.0
^F
DMDHCON
0.5
Dmd Level(-) Lo Cool Off
0.5 - 2
^F
DMDLCOFF
1
Cool Trend Demand Level
0.1 - 5
^F
CTRENDLV
0.1
Heat Trend Demand Level
0.1 - 5
^F
HTRENDLV
0.1
Cool Trend Time
30 - 600
sec
CTRENDTM
120
Heat Trend Time
30 - 600
sec
HTRENDTM
120
DMDL
Demand Limit Select
0 - 3
DMD_CTRL
0
Demand Limit at 20 ma
0 - 100
%
DMT20MA
100
Loadshed Group Number
0 - 99
SHED_NUM
0
Loadshed Demand Delta
0 - 60
%
SHED_DEL
0
Maximum Loadshed Time
0 - 120
min
SHED_TIM
60
Demand Limit Sw.1 Setpt.
0 - 100
%
DLSWSP1
80
Demand Limit Sw.2 Setpt.
0 - 100
%
DLSWSP2
50
ECON
Economizer Installed ?
Yes/No
ECON_ENA
Yes
Economizer Min.Position
0 - 100
%
ECONOMIN
20
Economizer Max.Position
0 - 100
%
ECONOMAX
98
Economzr trim for sumZ ?
Yes/No
ECONTRIM
Yes
Econ ChangeOver Select
0 - 3
ECON_SEL
1
OA Enthalpy ChgOvr Selct
1 - 5
OAEC_SEL
2
Outdr.Enth Compare Value
18 - 28
OAEN_CFG
24
High OAT Lockout Temp
55 - 120
dF
OAT_LOCK
60
OA Dewpoint Temp Limit
50 - 62
dF
OADEWCFG
55
Outside Air RH Sensor
Enable/Disable
OARHSENS
Disable
Economizer Control Type
1-3
ECON_CTL
1
Economizer Switch Config
0-2
ECOSWCFG
0
Economizer Prop.Gain
0.7 - 3.0
EC_PGAIN
1
Economizer Range Adjust
0.5 - 5
^F
EC_RANGE
2.5
Economizer Speed Adjust
0.1 - 10
EC_SPEED
0.75
Economizer Deadband
0.1 - 2
^F
EC_DBAND
0.5
Unoc Econ Free Cool Cfg
0-2
UEFC_CFG
0
Unoc Econ Free Cool Time
0-720
min
UEFCTIME
120
Un.Ec.Free Cool OAT Lock
40-70
dF
UEFCNTLO
50
EDTR
EDT Reset Configuration
0 - 3
EDRSTCFG
0
Reset Ratio
0 - 10
RTIO
2
Reset Limit
0 - 20
^F
LIMT
10
EDT 4-20 ma Reset Input
Enable/Disable
EDTRSENS
Disable
HEAT
Heating Control Type
0 - 4
HEATTYPE
0
Heating Supply Air Setpt
80-120
dF
SASPHEAT
85
Occupied Heating Enabled
Yes/No
HTOCCENA
No
MBB Sensor Heat Relocate
Yes/No
HTLATMON
No
Fan-off Delay, Gas Heat
45-600
GAS_FOD
45
Fan-off Delay, Elec Heat
10-600
ELEC_FOD
30
Staged Gas Heat Type
0 - 4
HTSTGTYP
0
Max Cap Change per Cycle
5 - 45
HTCAPMAX
45
S.Gas DB min.dF/PID Rate
0 - 5
HT_MR_DB
0.5
St.Gas Temp. Dead Band
0 - 5
^F
HT_SG_DB
2
Heat Rise dF/sec Clamp
0.05 - 0.2
HTSGRISE
0.06
LAT Limit Config
0 - 20
^F
HTLATLIM
10
Heat Control Prop. Gain
0 - 1.5
HT_PGAIN
1
Heat Control Derv. Gain
0 - 1.5
HT_DGAIN
1
Heat PID Rate Config
60 - 300
sec
HTSGPIDR
90
Summary of Contents for WEATHERMAKER 48AJ020
Page 95: ...95 Fig 13 Typical Main Control Box Wiring Schematic A48 7787 ...
Page 96: ...96 TO NEXT PAGE Fig 14 Auxiliary Control Box Wiring Schematic A48 7294 ...
Page 98: ...98 Fig 15 Typical 2 Stage Gas Heat Wiring Schematic Size 051 and 060 Units Shown A48 6866 ...
Page 102: ...102 TO NEXT PAGE Fig 18 Typical Power Schematic Size 051 and 060 Units Shown A48 7298 ...
Page 104: ...104 Fig 19 Controls Option Wiring Schematic A48 7810 ...
Page 105: ...105 Fig 20 Small Chassis Component Location Size 020 035 Units A48 7301 ...
Page 106: ...106 Fig 21 Large Chassis Component Locations Size 036 060 Units A48 7302 ...