POINT
NAME
POINT DESCRIPTION
I/O POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S)
PORT STATE
INPUTS
RMTIN
Remote occupancy
DI1
J4, 1-2
2
24VAC = 1, 0VAC = 0
ECONENBL,
ECOORIDE
Economizer enable
DI2
J4, 3-4
4
24VAC = 1, 0VAC = 0
RARH
Return air relative humidity
AN1
J5, 1-3
1=24VDC, 2=0-20mA in, 3=GND
0-20mA
OARH
Outdoor air relative humidity
AN2
J5, 4-6
4=24VDC, 5=0-20mA in, 6=GND
0-20mA
OUTPUTS
ECB1_AO1
ECB1, analog output 1
AO1
J9, 1-2
1=0-20mA, 2=GND
0-20mA OUT
ECONOCMD
Economizer actuator
(digital control)
PP/MP
J7, 1-3
1=PP/MP Data, 2=24VAC, 3=GND
Belimo PP/MP Protocol
PE_A
Power Exhaust stage A
RLY1
J8, 1-3
1 = 2 = RLY1A, 3 = RLY1B
1 = Closes RLY1A/RLY1B
PE_B
Power Exhaust stage B
RLY 2
J8, 4-6
4 =5 = RLY2A, 6 = RLY2B
1 = Closes RLY2A/RLY2B
PE_C
Power Exhaust stage C
RLY 3
J8, 7-9
7 = 8 = RLY3A, 9 = RLY3B
1 = Closes RLY3A/RLY3B
ECON_PWR
Economizer Power
RLY 6
J8, 16-18
16 = 17 = RLY6A, 18 = RLY6B
1 = Closes RLY6A/RLY6B
POINT
NAME
POINT DESCRIPTION
I/O POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S)
PORT STATE
INPUTS
DI1
J4, 1-2
2
24VAC = 1, 0VAC = 0
DI2
J4, 3-4
4
24VAC = 1, 0VAC = 0
BP
Building static pressure
AN1
J5, 1-3
1=24VDC, 2=0-20mA in, 3=GND
0-20mA
SP
Supply Duct static pressure
AN2
J5, 4-6
4=24VDC, 5=0-20mA in, 6=GND
0-20mA
OUTPUTS
SFAN_VFD
Supply Fan Inverter speed
AO1
J9, 1-2
1=0-20mA, 2=GND
0-20mA OUT
PP/MP
J7, 1-3
1=PP/MP Data, 2=24VAC, 3=GND
Belimo PP/MP Protocol
RLY1
J8, 1-3
1 = 2 = RLY1A, 3 = RLY1B
1 = Closes RLY1A/RLY1B
RLY 2
J8, 4-6
4 =5 = RLY2A, 6 = RLY2B
1 = Closes RLY2A/RLY2B
RLY 3
J8, 7-9
7 = 8 = RLY3A, 9 = RLY3B
1 = Closes RLY3A/RLY3B
MLV
Minimum load valve
RLY 6
J8, 16-18
16 = 17 = RLY6A, 18 = RLY6B
1 = Closes RLY6A/RLY6B
POINT
NAME
POINT DESCRIPTION
I/O POINT
NAME
PLUG AND PIN
REFERENCE
SIGNAL PIN(S)
PORT STATE
INPUTS
AN1
J5, 1-3
1=5v, 2=Vin, 3=GND (thermistor 1-2)
(0-5VDC, thermistor, ohms)
AN2
J5, 4-6
4=5v, 5=Vin, 6=GND (thermistor 4-5)
(0-5VDC, thermistor, ohms)
LAT1SGAS
Leaving air temperature 1
AN3
J5, 7-9
7=5v, 8=Vin, 9=GND (thermistor 7-8)
(0-5VDC, thermistor, ohms)
LAT2SGAS
Leaving air temperature 2
AN4
J5, 10-12
10=5v, 11=Vin, 12=GND (thermistor 10-11) (0-5VDC, thermistor, ohms)
LAT3SGAS
Leaving air temperature 3
AN5
J5, 13-15
13=5v, 14=Vin, 15=GND (thermistor 13-14) (0-5VDC, thermistor, ohms)
AN6
J6, 1-3
1=5v, 2=Vin, 3=GND (thermistor 1-2)
(0-5VDC, thermistor, ohms)
AN7
J6, 4-6
4=5v, 5=Vin, 6=GND (thermistor 4-5)
(0-5VDC, thermistor, ohms)
AN8
J6, 7-9
7=5v, 8=Vin, 9=GND (thermistor 7-8)
(0-5VDC, thermistor, ohms)
AN9
J7, 1-2
1
(thermistor, ohms)
AN10
J7, 3-4
3
(thermistor, ohms)
OUTPUTS
AO1
J8, 1-2
1=0-20mA, 2=GND
0-20mA OUT
AO2
J8, 3-4
3=0-20mA, 4=GND
0-20mA OUT
HS3
Heat Stage 3
RLY1
J9, 1-3
1 = 2 = RLY1A, 3 = RLY1B
1 = Closes RLY1A/RLY1B
HS4
Heat Stage 4
RLY 2
J9, 4-6
4 =5 = RLY2A, 6 = RLY2B
1 = Closes RLY2A/RLY2B
HS5
Heat Stage 5
RLY 3
J9, 7-9
7 = 8 = RLY3A, 9 = RLY3B
1 = Closes RLY3A/RLY3B
HS6
Heat Stage 6
RLY 4
J9, 10-12
10 = 11 = RLY4A, 12 = RLY4B
1 = Closes RLY4A/RLY4B
RLY 5
J9, 13-15
13 = 14 = RLY5A, 15 = RLY5B
1 = Closes RLY5A/RLY5B
Summary of Contents for WEATHERMAKER 48A4
Page 8: ...8 Fig 1 Component Arrangement 48 50A2 A3 A4 A5020 035 Units a48 8308 ...
Page 10: ...10 Fig 3 Power Schematic 48 50A2 A3 A4 A5020 050 Units a48 8385 ...
Page 11: ...11 Fig 4 Power Schematic 48 50A2 A3 A4 A5060 RTPF Units a48 8386 ...
Page 12: ...12 Fig 5 Power Schematic 48 50A2 A3 A4 A5060 MCHX Units a48 8387 ...
Page 13: ...13 TO NEXT PAGE Fig 6 Main Control Box Circuit 48 50A2 A3 A4 A5020 060 Units a48 8388 ...
Page 16: ...16 Fig 8 Controls Expansion Board Wiring 48 50A2 A3 A4 A5020 060 Units a48 8261 ...
Page 17: ...17 Fig 9 Gas Heat Control Circuit 2 Stage Heat 48A2 A3 A4 A5020 050 Units a48 8310 ...
Page 18: ...18 Fig 10 Gas Heat Control Circuit 2 Stage Heat 48A2 A3 A4 A5060 Units a48 8311 ...
Page 19: ...19 Fig 11 Gas Heat Control Circuit Staged Gas Heat 48A2 A3 A4 A5020 050 Units a48 8313 ...
Page 20: ...20 Fig 12 Gas Heat Control Circuit Staged Gas Heat 48A2 A3 A4 A5060 Units a48 8315 ...
Page 21: ...21 Fig 13 Electric Heat Control Circuit 50A2 A3 A4 A5020 050 Units a48 8266 ...
Page 22: ...22 Fig 14 Electric Heat Control Circuit 50A2 A3 A4 A5060 Units a48 8267 ...
Page 26: ......
Page 27: ......