Carrier WEATHERMAKER 48A4 Wiring Diagrams Download Page 3

3

SEQUENCE OF OPERATION

Constant Volume (CV) Units  — 

On power up, the

control module will activate the initialization software. The

initialization software will determine the unit configuration and

also initialize any controls loops and input/output devices. All

alarms and configurations are saved in memory and maintained

during power outages. All alarms will be maintained in

memory and must be cleared through the scrolling marquee

display.

The unit can be configured with two different control types:

thermostat control or space temperature sensor control.
THERMOSTAT CONTROL — If the unit is equipped with a

thermostat with Y1, Y2, W1, W2 and G connections, then the

control will perform the following sequence. 

When terminal G is energized, the indoor fan will turn on.

The fan must be running for heating or cooling to occur. If Y1

is closed (first stage of cooling is energized), then the unit

control will first check the ability to use the economizer. If the

economizer can be used, then the unit control will modulate the

damper open to maintain the low-load economizer leaving air

temperature set point.

If Y2 closes (second stage of cooling is energized), then the

unit control will lower the leaving air temperature set point to

the configured set point. If the economizer cannot satisfy the

load, then the compressors will be sequenced on to maintain

either the low or high load temperature set points. If the

economizer cannot be used or the enable control disables the

economizer, then the control will sequence the compressors

based on the Y1 and Y2 signals.

If two-stage control has been selected, then the unit control

will map the compressors to the Y1 and Y2 inputs (first and

second stage cooling) as defined in the loading sequence. If

Adaptive mode has been selected, then the control will add and

remove compressor stages to maintain the high and low

demand set points. If Y1 is closed (first stage of cooling

energized), at least one compressor stage will be turned on.

If W1 closes (first stage of heating is energized), then the

unit will be in the Heating mode. The economizer will be

closed to the minimum position. If the unit is equipped with

gas or electric heat, then the first stage of heat will be

energized. If W2 closes, then the unit control will turn on the

second stage of heat. If the unit is equipped with a staged gas

heat control option, then the W1 and W2 signal will be used to

control the gas heat to the configurable low and high heat load

leaving air temperature set points. If the unit is equipped with

gas heat, then the integrated gas control (IGC) board will con-

trol the operation of the gas heat. See the Gas Heat Unit Opera-

tion section for the IGC board sequence of operation.
SPACE TEMPERATURE SENSOR CONTROL — If space

temperature operation has been selected using a T55, T56, or

T58 sensor, then a wire jumper must be added between R, W1,

and W2. If a remote occupancy control method has been

selected, then the remote occupancy input must first be closed

for the unit to go into heating, vent, or cooling modes. If the

internal timeclock is used, the unit control module determines

the occupancy state based on the system time schedules.

If Temperature Compensated Start is active, the unit will

be controlled as in the occupied mode. The Temperature

Compensated Start function will start the unit before the

scheduled occupied time (as determined by prior operation) to

bring the space to the set point temperature when occupied

time starts. As an example, if the unoccupied set point is 60 F,

the occupied set point is 72 F, and the occupied time period

starts at 8:00 AM, the Temperature Compensated Start function

will bring on the unit at 7:45 AM (as determined from previous

operation) so the room temperature will be at 72 F when the

occupied time starts.

If the unit has been configured for a pre-occupancy purge,

then the control will start the unit in Vent mode prior to the

occupancy time to vent the space. If an IAQ (indoor air quality)

sensor is being used and the low IAQ set point is satisfied, then

the occupancy Purge mode will be terminated.

The set points for heat and cooling are configurable through

the scrolling marquee display.
NOTE: If a T56 sensor is being used, then the slide bar on the

sensor can offset the set point by has much as 5 degrees.

If the space temperature rises above the cooling set point,

then the unit will go into Cooling mode. If the economizer can

be used, the control will first try to control to the Leaving

Air Temperature set point. The set point will depend on the

space temperature. If the temperature is above the Low

Demand set point, then the Low Economizer Load Discharge

Air Temperature set point will be used. If the temperature is

above the High Load Space Temperature set point, then the

High Load Leaving Air Temperature set point will be used. If

the economizer cannot satisfy the load the compressors will

be sequenced on to maintain either the low or high load

temperature set points. If the economizer cannot be used or the

unit control disables the economizer, then the unit control will

sequence the compressors based on the low and high load

space temperature variables. If two-stage control has been

selected then the control will map the compressors to the low

and high loads as defined in the loading sequence. If Adaptive

mode has been selected then the control will add and remove

compressors stages to maintain the low and high demand

leaving air set points.

If the load goes below the heating space temperature set

points, the Heating mode will initiate. The economizer will be

closed to the minimum position and (if the unit is equipped

with gas or electric heat) the first stage of heat will be

energized. If the space temperature goes below the High Load

Space Temperature set point then the control will turn on the

second stage of heat. If the unit is equipped with a staged gas

heat control option then the low load and high load demand

signal will control the Leaving Air Temperature set point and

will turn on heating stages to maintain the Leaving Air

Temperature set points.

If the unit is configured for unoccupied free cooling,

mechanical cooling, or heating and the room temperature goes

above or below the unoccupied configuration set points, then

the unit control will turn on free cooling, mechanical cooling,

or heat as needed to return room temperature within the

unoccupied set points. When in this mode, the economizer

dampers will be maintained fully closed or to the minimum

unoccupied ventilation set point.

Variable Air Volume Control — 

On power up, the

control module will activate the initialization software. The

initialization software will determine the unit configuration and

also initialize any control loops and input/output devices. All

alarms and configurations are saved in memory and maintained

during power outages. All alarms will be maintained in

memory and must be cleared through the scrolling marquee

display.

The unit will first determine the mode of operation. If the

unit has been configured for space temperature demand then

the control will determine, based on the configurable set points,

if the unit should be in the Heating mode, Vent mode or Cool-

ing mode. If the unit is configured for return air temperature

control, then the unit control will start the fan and monitor the

return air temperature against the configurable set point to

determine if the unit should be in Cooling, Vent or Heating

mode.

Summary of Contents for WEATHERMAKER 48A4

Page 1: ...79 9 48A2 A3 A4 A5060 48EJ503679 10 Gas Heat Control Circuit Staged Gas Heat 48A2 A3 A4 A5020 050 48EJ502488 11 48A2 A3 A4 A5060 48EJ503680 12 Electric Heat Control Circuit 50A2 A3 A4 A5020 050 48EJ503080 13 50A2 A3 A4 A5060 48EJ503655 14 ACCESSORY UNIT FIG NO Motormaster V Low Ambient Controller 48 50A2 A3 A4 A5020 035 15 48 50A2 A3 A4 A5040 050 AND 060 RTPF Units 16 48 50A2 A3 A4 A5060 MCHX Unit...

Page 2: ...riable Frequency Drive Terminal Block Terminal Unmarked Terminal Marked Splice Factory Wiring Field Wiring To indicate common potential only not to represent wiring To indicate FIOP or Accessory Common PLUG LOCATION REFERENCE NOTES 1 Factory wiring is in accordance with the national electrical codes Any field modifications or additions must be in compliance with all applicable codes 2 Use 75 C min...

Page 3: ...nsated Start function will bring on the unit at 7 45 AM as determined from previous operation so the room temperature will be at 72 F when the occupied time starts If the unit has been configured for a pre occupancy purge then the control will start the unit in Vent mode prior to the occupancy time to vent the space If an IAQ indoor air quality sensor is being used and the low IAQ set point is sat...

Page 4: ...th gas valves are energized and both IGC boards initiate spark All of the gas heating control is performed through the IGC boards located in the heating section The MBB Main Base Board module board initiates and terminates heating operation and monitors the status of the requirements for indoor fan operation The fan will be controlled directly by the MBB board When the thermostat or room sensor ca...

Page 5: ...c 1 0vac Y2 Thermostat Y2 input DI6 J7 7 8 8 0 24vac 1 0vac Y1 Thermostat Y1 input DI7 J7 9 10 10 0 24vac 1 0vac CSB_A1 Compressor A1 current sensor DIG1 J9 10 12 10 5v 11 Vin 12 GND 0 5vdc 1 0vdc CSB_A2 Compressor A2 current sensor DIG2 J9 7 9 7 5v 8 Vin 9 GND 0 5vdc 1 0vdc CSB_B1 Compressor B1 current sensor DIG3 J9 4 6 4 5v 5 Vin 6 GND 0 5vdc 1 0vdc CSB_B2 Compressor B2 current sensor DIG4 J9 1...

Page 6: ...pply Fan Inverter speed AO1 J9 1 2 1 0 20mA 2 GND 0 20mA OUT PP MP J7 1 3 1 PP MP Data 2 24VAC 3 GND Belimo PP MP Protocol RLY1 J8 1 3 1 2 RLY1A 3 RLY1B 1 Closes RLY1A RLY1B RLY 2 J8 4 6 4 5 RLY2A 6 RLY2B 1 Closes RLY2A RLY2B RLY 3 J8 7 9 7 8 RLY3A 9 RLY3B 1 Closes RLY3A RLY3B MLV Minimum load valve RLY 6 J8 16 18 16 17 RLY6A 18 RLY6B 1 Closes RLY6A RLY6B POINT NAME POINT DESCRIPTION I O POINT NAM...

Page 7: ...gic 8 Grd ground TB 4 THEROMSTAT CONNECTIONS HY84HA090 in Main Control Box TB4 1 Thermostat R 24 VAC Power 2 Thermostat Y1 24 VAC Input 3 Thermostat Y2 24 VAC Input 4 Thermostat W1 24 VAC Input 5 Thermostat W2 24 VAC Input 6 Thermostat G 24 VAC Input 7 Thermostat C 24 VAC Common 8 Thermostat X Alarm Contact 24 VAC Output TB 5 FIELD CONNECTIONS HY84HA101 in Main Control Box TB5 1 VAV Heater Interlo...

Page 8: ...8 Fig 1 Component Arrangement 48 50A2 A3 A4 A5020 035 Units a48 8308 ...

Page 9: ...nent Arrangement 48 50A2 A3 A4 A5040 060 Units a48 8309 LOCATIONS ARE TYPICAL FOR ALL SIZE 040 060 UNITS SIZE 060 RTPF ROUND TUBE PLATE FIN UNITS HAVE 6 SIX OUTDOOR FAN ASSEMBLIES UNIT SHOWN IS A 50 SERIES SIZE 040 ...

Page 10: ...10 Fig 3 Power Schematic 48 50A2 A3 A4 A5020 050 Units a48 8385 ...

Page 11: ...11 Fig 4 Power Schematic 48 50A2 A3 A4 A5060 RTPF Units a48 8386 ...

Page 12: ...12 Fig 5 Power Schematic 48 50A2 A3 A4 A5060 MCHX Units a48 8387 ...

Page 13: ...13 TO NEXT PAGE Fig 6 Main Control Box Circuit 48 50A2 A3 A4 A5020 060 Units a48 8388 ...

Page 14: ...14 TO PREVIOUS PAGE a48 8389 Fig 6 Main Control Box Circuit 48 50A2 A3 A4 A5020 060 Units cont ...

Page 15: ...15 ABB ACS800 DRIVE NOT USED ABB ACS550 DRIVE STANDARD TOSHIBA E3 DRIVE NOT USED Fig 7 Auxiliary Control Box Wiring 48 50A2 A3 A4 A5020 060 Units a48 8390 ...

Page 16: ...16 Fig 8 Controls Expansion Board Wiring 48 50A2 A3 A4 A5020 060 Units a48 8261 ...

Page 17: ...17 Fig 9 Gas Heat Control Circuit 2 Stage Heat 48A2 A3 A4 A5020 050 Units a48 8310 ...

Page 18: ...18 Fig 10 Gas Heat Control Circuit 2 Stage Heat 48A2 A3 A4 A5060 Units a48 8311 ...

Page 19: ...19 Fig 11 Gas Heat Control Circuit Staged Gas Heat 48A2 A3 A4 A5020 050 Units a48 8313 ...

Page 20: ...20 Fig 12 Gas Heat Control Circuit Staged Gas Heat 48A2 A3 A4 A5060 Units a48 8315 ...

Page 21: ...21 Fig 13 Electric Heat Control Circuit 50A2 A3 A4 A5020 050 Units a48 8266 ...

Page 22: ...22 Fig 14 Electric Heat Control Circuit 50A2 A3 A4 A5060 Units a48 8267 ...

Page 23: ...1 TB2 575 3 60 TB1 TB2 208 3 60 TB13A TB2 3 Add FR relay in parallel with OFC1 Fig 16 Motormaster V Accessory Wiring 48 50A2 A3 A4 A5040 050 and 48 50A2 A3 A4 A5060 RTPF Units NOTES 1 Motormaster control to be wired directly to CCB cir cuit breaker and the OFC1 contactor should be removed from the wiring 2 Connect start relay FR to the following terminals 230 3 60 TB1 TB2 460 3 60 TB1 TB2 575 3 60...

Page 24: ...5060 MCHX Units LEGEND CCB Control Circuit Breaker FR Fan Relay MM F Motormaster V Fuses MMPT Motormaster V Pressure Transducer MMV Motormaster V OFC Outdoor Fan Contactor OFM Outdoor Fan Motor TB Terminal Block NOTES 1 Motormaster control to be wired directly to CCB circuit breaker and the OFC1 contactor should be removed from the wiring 2 Connect start relay FR to the following terminals 230 3 6...

Page 25: ...E 060 36 kW 575 V SIZES 020 050 54 kW 575 V SIZE 060 72 kW 575 V SIZES 020 050 108 kW 575 V SIZE 060 Fig 19 Electric Heater Power Diagrams 72 kW 460 V SIZES 020 050 49 kW 380 V SIZES 020 050 108 kW 460 V SIZE 060 74 kW 380 V SIZE 060 a48 6694 a48 6695 a48 6696 a48 6697 a48 6698 a48 6699 LEGEND FU Fuse HC Heater Contactor TB Terminal Block Terminal Marked Terminal Block Terminal Unmarked Factory Wi...

Page 26: ......

Page 27: ......

Page 28: ... to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 56480002 01 Printed in U S A Form 48 50A 3W Pg 28 508 4 08 Replaces New Copyright 2008 Carrier Corporation ...

Reviews: