PRESSURES
Refrigerant Suction
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Refrigerant Discharge
CIRCUIT A _____________ PSIG
CIRCUIT B _____________ PSIG
Verify Refrigerant Charge using Charging Charts (Y/N) _____
GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____
Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____
IV. HUMIDI-MIZER
®
START-UP
NOTE: Units equipped with either SystemVu™ or RTU Open controls have Service Test menus or modes that can assist with the
Humidi-MiZer System Start-Up function and provide the means to make the observations listed for this start-up.
STEPS
1. Check CTB for jumper 5, 6, 7 (Jumper 5, 6, 7 must be cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure
_______________ PSIG
B. Discharge pressure
_______________ PSIG
C. Entering air temperature
_______________ ° F
D. Liquid line temperature at outlet or reheat coil
_______________ ° F
E. Confirm correct rotation for compressor (Y/N) _____
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Check unit charge per charging chart (Y/N) _____
(Jumper 32L Motormaster
®
temperature sensor during this check. Remove jumper when complete.)
5. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed (Y/N) _____
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____
B. Discharge pressure unchanged (Y/N) _____
C. Liquid temperature drops to 50 to 55°F range (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level (Y/N) _____
B. Discharge pressure decreases (35 to 50 psi) (Limited by Motormaster control) (Y/N) _____
C. Liquid temperature returns to normal cooling level (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
E. DSV solenoid energized, valve opens (Y/N) _____
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore set-points for thermostat and humidistat (Y/N) _____
REPEAT PROCESS FOR 2 COMPRESSOR SYSTEMS.
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......