72
b. Press ▼ (Down arrow key) once. The following dis
-
play appears:
c. Press
OK
. The following display appears:
d. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
e. Press ▼ (Down arrow key) again. The following dis
-
play appears:
f. Press ▼ (Down arrow key) again. The following dis
-
play appears:
g. Press ▼ (Down arrow key) again. The following dis
-
play appears:
NOTE: By pressing
OK
the number in the bracket can be changed
until the desired number appears. Press
OK
again to set the select
-
ed value.
11. Set Analog Inputs:
a. Press the
Back
key until the following display
appears:
b. Press ▼ (Down arrow key) until the following dis
-
play appears:
c. Press
OK
. The following display appears:
d. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
e. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
f. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
g. Press ▼ (Down arrow key) once to move the high
-
light to the bottom row, then press
OK
. The following
display appears:
12. Set Reset Mode and RFI Filter:
a. Press the
Back
key until the following display
appears:
b. Press ▼ (Down arrow key) until the following dis
-
play appears:
c. Press
OK
. The following display appears:
d. Press ▼ (Down arrow key) twice. The following dis
-
play appears:
e. Press
OK
. The following display appears:
f. Press
OK
to highlight the number in the bracket.
g. Use the ▲ (Up arrow) and ▼ (Down arrow) keys to
change the number to 3 for 2 automatic resets; then
press
OK
. The display changes to:
h. Press ▼ (Down arrow key) once. The following dis
-
play appears:
i. Press
OK
to highlight the number of seconds and use the
▲ (Up arrow) and ▼ (Down arrow) keys to select
600 seconds. Press
OK
again to set the selected value.
j. Press the
Back
key once. The following display
appears:
k. Press ▼ (Down arrow key) twice. The following dis
-
play appears:
l. Press
OK
. The following display appears:
m. Press
OK
to highlight the number in the brackets and use
the ▲ (Up arrow) and ▼ (Down arrow) keys to select
0. Press
OK
again to set the selected value.
13. Complete reprogramming: Press the
Auto On
key before
disconnecting the VFD Remote Keypad from the variable
frequency drive.
4—** Limits/Warnings
5—** Digital In/Out
5 —0* Digital I/O Mode
5 —1* Digital Inputs
5 —10 Terminal 18 Digital In...
[8] Start
5 —11 Terminal 19 Digital In...
[16] Preset ref bit 0
5 —12 Terminal 27 Digital In...
[17] Preset ref bit 1
5 —12 Terminal 29 Digital In...
[18] Preset ref bit 2
4—** Limits/Warnings
5—** Digital In/Out
5—** Digital In/Out
6—** Analog In/Out
6—**Analog In/Out
6—1* Analog Input 53
6 —10 Terminal 53 Low Voltage
2V
6 —11 Terminal 53 High Voltage
[10V]
6 —14 Set Min Reference
[0 Hz]
6 —15 Set Max Reference
[60 Hz]
0 —** Operation/Display
1 —** Load and Motor
13—** Smart Logic
14—** Special Functions
14 —0* Inverter Switching
14 —1* Mains On/Off
14—1* Mains On/Off
14—2* Reset Functions
14 —20 Reset Mode
[0] Manual reset
14 —20 Reset Mode
[3] Automatic reset x 3
24 —21 Automatic Restart T...
10s
14—1* Mains On/Off
14—2* Reset Functions
14—4* Energy Optimizing
14—5* Environment
14 —50 RFI Filter
[1] On
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......