All Units --
All field wiring must comply with NEC and all local code
requirements.
Size wire based on MCA (Minimum Circuit Amps) on the
unit informative plate. See Fig. 33 for power wiring
connections to the unit power terminal block and equipment
ground. Maximum wire size is 2/0 AWG per pole.
11
13
L1
L2
L3
Ground
(GR)
TB1
208/230-3-60
460-3-60
575-3-60
T1
T2
T3
L1
L2
L3
L1
L2
L3
Factory
Wiring
Disconnect
per NEC
Optional
Disconnect
Switch
or HACR
12
Equip
GR Lug
Ground
(GR)
Equip
GR Lug
Units Without Disconnect or HACR Option
Units With Disconnect or HACR Option
C12387
Fig. 33 -- Power Wiring Connections
Provide a ground--fault and short--circuit over--current
protection device (fuse or breaker) per NEC Article 440
(or local codes). Refer to unit informative data plate for
MOCP (Maximum Over--current Protection) device size.
NOTE
: Units ordered with factory--installed HACR do
not need additional ground--fault and short circuit over
current protection device unless required by local codes.
Voltage to compressor terminals during operation must be
within voltage range indicated on unit nameplate. See
Tables 26 and 27. On 3--phase units, voltages between
phases must be balanced within 2% and the current within
10%. Use the formula shown in the legend for Tables 26
and 27 (see Note 3 on page 79) to determine the percent
of voltage imbalance.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to
electrical components. Such operation would invalidate
any applicable Carrier warranty.
CAUTION
!
Convenience Outlets —
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Lock--out and tag--out this switch, if necessary.
!
WARNING
Two types of convenience outlets are offered on 48LC
models: Non--unit powered and unit--powered. Both types
provide a 125--volt GFCI (ground--fault circuit--interrupter)
duplex receptacle rated at 15--A behind a hinged access
cover, located on the corner panel of the unit. See Fig. 34.
Convenience
Outlet
Electric
Disconnect
Switch
Control Box
Access Panel
C10641
Fig. 34 -- Convenience Outlet Location
Installing
Weatherproof
Cover:
A
weatherproof
while-in-use cover for the factory-installed convenience
outlets is now required by UL standards. This cover cannot
be factory-mounted due to its depth; it must be installed at
unit installation. For shipment, the convenience outlet is
covered with a blank cover plate.
The weatherproof cover kit is shipped in the unit’s control
box. The kit includes the hinged cover, a backing plate
and gasket.
DISCONNECT
ALL
POWER
TO
UNIT
AND
CONVENIENCE OUTLET. LOCK--OUT AND TAG--OUT
ALL POWER.
Remove the blank cover plate at the convenience outlet;
discard the blank cover.
Summary of Contents for WeatherExpert 48LC
Page 5: ...5 C13057 Fig 2 Unit Dimensional Drawing 14 Size Unit Sheet 1 of 3 ...
Page 6: ...6 C13058 Fig 2 cont Unit Dimensional Drawing 14 Size Unit Sheet 2 of 3 ...
Page 7: ...7 C13059 Fig 2 cont Unit Dimensional Drawing 14 Size Unit Sheet 3 of 3 ...
Page 8: ...8 C13032 Fig 3 Unit Dimensional Drawing 17 and 20 Size Units Sheet 1 of 3 ...
Page 9: ...9 C13033 Fig 3 cont Unit Dimensional Drawing 17 and 20 Size Units Sheet 2 of 3 ...
Page 10: ...10 C13034 Fig 3 cont Unit Dimensional Drawing 17 and 20 Size Units Sheet 3 of 3 ...
Page 11: ...11 C14106 Fig 4 Unit Dimensional Drawing 24 and 26 Size Units Sheet 1 of 3 ...
Page 12: ...12 C14107 Fig 4 cont Unit Dimensional Drawing 24 and 26 Size Units Sheet 2 of 3 ...
Page 13: ...13 C14108 Fig 4 cont Unit Dimensional Drawing 24 and 26 Size Units Sheet 3 of 3 ...
Page 17: ...17 C13054 Fig 8 Roof Curb Details 14 Size Unit ...
Page 18: ...18 C13055 Fig 9 Roof Curb Details 17 and 20 Size Units ...
Page 19: ...19 C13056 Fig 10 Roof Curb Details 24 and 26 Size Units ...
Page 27: ...27 a48 9336 Fig 26 48LC 14 26 Electro mechanical Control Wiring Diagram ...
Page 28: ...28 a48 9337 Fig 27 48LC 14 26 RTU Open Control Wiring Diagram ...
Page 29: ...29 a48 9338 Fig 28 48LC 14 26 SystemVut Control Wiring Diagram ...
Page 31: ...31 a48 9339 Fig 30 Typical Power Wiring Diagram SystemVut Controls 48LC 26 208 230V Shown ...
Page 58: ...58 a48 9340 Fig 55 Typical EconoMi erR X Wiring Diagram ...