Legend and Notes for Tables 26 and 27
LEGEND:
BRKR
---
Circuit breaker
C.O.
---
Convenience outlet
DISC.
---
Disconnect
FLA
---
Full load amps
LRA
---
Locked rotor amps
MCA
---
Minimum circuit amps
P.E.
---
Power exhaust
Pwrd fr/ unit
---
Powered from unit
PWRD C.O.
---
Powered convenience outlet
UNPWR C.O. ---
Unpowered convenience outlet
NOTES
:
1. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device
for the unit shall be fuse or HACR breaker. Canadian units may be fuse or circuit
breaker.
2. For 208/230 v units, where one value is shown it is the same for either 208 or
230 volts.
3.
Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Average Voltage =
(224 + 231 + 226)
=
681
3
3
=
227
Determine maximum deviation from average voltage.
(AB) 227 – 224 = 3 v
(BC) 231 – 227 = 4 v
(AC) 227 – 226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
4
227
= 1.76%
This amount of phase imbalance is satisfactory as it is below the maximum
allowable 2%.
IMPORTANT
: If the supply voltage phase imbalance is more than 2%, contact
your local electric utility company immediately.
Summary of Contents for WeatherExpert 48LC
Page 5: ...5 C13057 Fig 2 Unit Dimensional Drawing 14 Size Unit Sheet 1 of 3 ...
Page 6: ...6 C13058 Fig 2 cont Unit Dimensional Drawing 14 Size Unit Sheet 2 of 3 ...
Page 7: ...7 C13059 Fig 2 cont Unit Dimensional Drawing 14 Size Unit Sheet 3 of 3 ...
Page 8: ...8 C13032 Fig 3 Unit Dimensional Drawing 17 and 20 Size Units Sheet 1 of 3 ...
Page 9: ...9 C13033 Fig 3 cont Unit Dimensional Drawing 17 and 20 Size Units Sheet 2 of 3 ...
Page 10: ...10 C13034 Fig 3 cont Unit Dimensional Drawing 17 and 20 Size Units Sheet 3 of 3 ...
Page 11: ...11 C14106 Fig 4 Unit Dimensional Drawing 24 and 26 Size Units Sheet 1 of 3 ...
Page 12: ...12 C14107 Fig 4 cont Unit Dimensional Drawing 24 and 26 Size Units Sheet 2 of 3 ...
Page 13: ...13 C14108 Fig 4 cont Unit Dimensional Drawing 24 and 26 Size Units Sheet 3 of 3 ...
Page 17: ...17 C13054 Fig 8 Roof Curb Details 14 Size Unit ...
Page 18: ...18 C13055 Fig 9 Roof Curb Details 17 and 20 Size Units ...
Page 19: ...19 C13056 Fig 10 Roof Curb Details 24 and 26 Size Units ...
Page 27: ...27 a48 9336 Fig 26 48LC 14 26 Electro mechanical Control Wiring Diagram ...
Page 28: ...28 a48 9337 Fig 27 48LC 14 26 RTU Open Control Wiring Diagram ...
Page 29: ...29 a48 9338 Fig 28 48LC 14 26 SystemVut Control Wiring Diagram ...
Page 31: ...31 a48 9339 Fig 30 Typical Power Wiring Diagram SystemVut Controls 48LC 26 208 230V Shown ...
Page 58: ...58 a48 9340 Fig 55 Typical EconoMi erR X Wiring Diagram ...