PROCEDURE 2—UNIT INSTALLATION

1. Drill or cut a 7/8-in. hole for each UV lamp into the coil casing, casing door or the connecting ductwork.

2. Securely mount UV lamp base assembly to the flat surface selected in Procedure 1 (use screws provided).

3. Replace coil casing door and slide ballast/lamp assembly into the mounted base, making sure the locating stud and molex connectors are

aligned (See Fig. 2).

4. Install fastener screw to hold lamp/ballast to base.

5. Replace plastic cover(s) on UV lamp assembly base to complete the installation.

NOTE:

On furnace application—Use 115-v power source other than the furnace motor circuit.

NOTE:

On fan coil application—Use 208/230-v power source other than the fan coil motor circuit.

6. Adhere warning label with install date and change dates (329734-101 RevA) to indoor coil casing door. The label is included in the carton

with the lamp(s).

7. Connect electrical cord to suitable electrical receptacle.

UV LAMP START-UP PROCEDURES

1. After power is supplied to lamp(s), make sure the LEDs behind the logo are illuminated. If not, verify supply voltage.

NOTE:

On 2 lamp models, both lamp/ballast assemblies need to be installed before lamps will illuminate.

2. If at any time the LED lights behind the logo are dim this is an indiction that one of the UV lamps is not working. Disconnect power and

inspect for proper lamp operation.

UV LAMP CARE AND MAINTENANCE

CAUTION: MINOR BURN HAZARD

Failure to follow this caution may result in minor personal injury.
Allow lamp to cool for 1–minute before opening UV lamp casing or HVAC unit cabinet.

NOTE:

The recommended life of the lamp assembly in this UV lamp product is 1-year of constant operation or a maximum of 9,000 hours of

unit runtime.

1. When replacement of lamp is needed, order proper lamp assembly (See Table 2) from your dealer / distributor.

2. Disconnect power supply from UV lamp by unplugging the electrical cord.

3. Remove protective cover from UV lamp assembly.

Table 2—Replacement Lamp Ordering Information

REPLACEMENT LAMP ORDER NUMBERS

Quantity

Lamp Voltage

ODS Number

1 Lamp/Ballast Assembly

115-1-60

UVLXXRPL1020

1 Lamp/Ballast Assembly

208/230-1-60

UVLXXRPL3020

CAUTION: MERCURY EXPOSURE HAZARD

Failure to follow this caution may result in minor personal injury.
Lamp contains a small quantity of mercury. Handle with care. If a lamp breaks, clean and dispose with care.

4. Remove fastener screw(s) that holds lamp/ballast to base.

5. Gently pull lamp assembly from mounted base assembly.

6. Place old lamp assembly in a safe area before proceeding.

NOTE:

Treat the disposal of these lamps as you would a standard fluorescent lamp.

7. Carefully slide new lamp/ballast assembly into base assembly until fully seated, retighten fastener screw(s) to hold new lamp in base.

8. Replace protective cover.

9. Reconnect unit power to UV lamp.

10. Observe that LEDs behind logo brightly illuminate and that the lamp(s) are operational.

NOTE:

Lamp/Ballast assembly should be removed when mounted on indoor coil casing door, if door is to be removed for system maintenance.

WARRANTY STATEMENT

This UV lamp Product is covered by a limited warranty. Please see the included warranty card for clarification.

—3—

Summary of Contents for UVLCC1LP

Page 1: ... signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage NOTE is used to hig...

Page 2: ...e to follow this caution could result in damage to unit or personal injury Perform visual inspection of potential mounting location by removing unit cabinet door prior to cutting or drilling Be careful not to cut drill or drive screws into coil refrigerant lines or other objects inside the HVAC unit NOTE On indoor coils 2 tons or smaller it is recommended that this UV lamp be installed in the conn...

Page 3: ...llow lamp to cool for 1 minute before opening UV lamp casing or HVAC unit cabinet NOTE The recommended life of the lamp assembly in this UV lamp product is 1 year of constant operation or a maximum of 9 000 hours of unit runtime 1 When replacement of lamp is needed order proper lamp assembly See Table 2 from your dealer distributor 2 Disconnect power supply from UV lamp by unplugging the electrica...

Page 4: ...C03004 Fig 2 UV Lamp Assembly Detail View Lamp Base LED Lights Lamp Ballast Assembly Note LED Lights are not lamp change indicators Lamps should be changed annually 4 ...

Page 5: ...2 Fig 3A Typical Furnace Coil Mounting Locations 115 v Application Horizontal N Coil Wide 042 048 060 060A A Coil Side View Standard A Coil Suggested Mounting Locations Front of Coil Casing Standard N Coil 5 ...

Page 6: ...C03021 Fig 3B Alternate Furnace Coil Mounting Locations 115 v Application Small N Coil Small A Coil Alternate Mounting Locations 6 ...

Page 7: ...C04014 Fig 3C Fan Coil Mounting Locations 208 230 v Application Sloped Fan Coil A Coil in Fan Coil Single Lamp Application Sloped Fan Coil Dual Lamp Application 7 ...

Page 8: ... 2018 CAC BDP 7310 W Morris St Indianapolis IN 46231 8 Form No 00001398 Catalog No IM UVLCR 01 ...

Reviews: