background image

INTRODUCTION

This UV Lamp system is designed to inhibit fungus and microbial growth when applied to the indoor coil/drain pan area of a central cooling
system. This system should be mounted on a flat surface. These instructions cover the installation of both the 1 and 2 lamp models. Lamps are
designed to operate for

one year

continuously before replacement is required.

NOTE:

These UV Lamps are designed for indoor use only.

This model consists of individual UV Lamp assemblies. On 2 lamp models, the 2 assemblies are connected by a flexible cord which will allow
the installer to separate the lamps from 4-in. to 18-in.

CAUTION: UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage to the product.
Do not touch glass section of UV Lamp without clean gloves. Damage to lamp will result. Oil from fingers will permanently
etch glass of lamp and weaken structure. Clean lamp with rubbing alcohol and clean cloth if necessary.

CAUTION: MERCURY EXPOSURE HAZARD

Failure to follow this caution may result in minor personal injury.
Lamp contains a small quantity of mercury. Handle with care. If a lamp breaks, clean and dispose with care.

NOTE:

The health aspects associated with the use of this product and its ability to aid in disinfection of environmental air have not been

investigated by UL.

NOTE:

Each lamp model kit includes cleaning kit and mounting screws.

INSTALLATION

PROCEDURE 1—UNIT MOUNTING LOCATION

WARNING: ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in electrical shock and cause injury or death.
Before installing accessory or performing maintenance or service on this or any other accessory, turn off main power to unit
and install lock-out tag. There may be more than one disconnect switch.

CAUTION: UNIT DAMAGE HAZARD

Failure to follow this caution could result in damage to unit or personal injury.
Perform visual inspection of potential mounting location by removing unit/cabinet door prior to cutting or drilling. Be careful
not to cut, drill or drive screws into coil, refrigerant lines or other objects inside the HVAC unit.

NOTE:

On indoor coils 2 tons or smaller it is recommended that this UV lamp be installed in the connecting ductwork above the indoor coil and

not in the coil casing itself.

NOTE:

No testing has been done to determine the effects of UV light on duct board or flex duct, metal duct is recommended.

NOTE:

It is recommended that a 7/8-in. hole be used for mounting this accessory. Using a 7/8-in. hole should provide proper clearances.

NOTE:

Components contained in the current furnace and fan coil equipment are resistant to UVC exposure. Color shift or chalking may occur

without affecting structural properties.

IMPORTANT:

Select a mounting location that prevents direct exposure to non-fiberglass media filters. A minimum distance of 6 feet is

recommended (Non-Fiberglass media will break down from UV exposure).

1. Turn off all power to unit and install lock-out tag.

2. Remove indoor coil casing door and inspect coil casing for proper location of UV lamp mounting holes.

3. Select location for lamp(s) that gives the most exposure to coil/drain pan. Light from the lamp should “wash” the coil and pan for maximum

effectiveness (See Fig. 3A, 3B or 3C).

Table 1— Unit Data

UNIT INFORMATION

1 LAMP MODEL

2 LAMP MODEL

1 LAMP MODEL

2 LAMP MODEL

Electrical

(V-PH-Hz)

115-1-60

115-1-60

208/230–1–60

208/230–1–60

Maximum Lamp Amperage Draw

0.6 Amps

1.1 Amps

0.3 Amps

0.6 Amps

Average Power Consumption

27 Watts

53 Watts

27 Watts

53 Watts

Unit Service

Cord

6 foot cord

with ground pin plug

Average Lamp Life

Approximately 1 Year or

9,000 Hours of Unit Runtime

Initial UVC Output at 1 Meter

(in microwatts per square centimeter and 70 Deg F)

and 450 FPM Airflow

105

198

105

198

Lamp Length

19-in.

—2—

Summary of Contents for UVLCC1LP

Page 1: ... signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage NOTE is used to hig...

Page 2: ...e to follow this caution could result in damage to unit or personal injury Perform visual inspection of potential mounting location by removing unit cabinet door prior to cutting or drilling Be careful not to cut drill or drive screws into coil refrigerant lines or other objects inside the HVAC unit NOTE On indoor coils 2 tons or smaller it is recommended that this UV lamp be installed in the conn...

Page 3: ...llow lamp to cool for 1 minute before opening UV lamp casing or HVAC unit cabinet NOTE The recommended life of the lamp assembly in this UV lamp product is 1 year of constant operation or a maximum of 9 000 hours of unit runtime 1 When replacement of lamp is needed order proper lamp assembly See Table 2 from your dealer distributor 2 Disconnect power supply from UV lamp by unplugging the electrica...

Page 4: ...C03004 Fig 2 UV Lamp Assembly Detail View Lamp Base LED Lights Lamp Ballast Assembly Note LED Lights are not lamp change indicators Lamps should be changed annually 4 ...

Page 5: ...2 Fig 3A Typical Furnace Coil Mounting Locations 115 v Application Horizontal N Coil Wide 042 048 060 060A A Coil Side View Standard A Coil Suggested Mounting Locations Front of Coil Casing Standard N Coil 5 ...

Page 6: ...C03021 Fig 3B Alternate Furnace Coil Mounting Locations 115 v Application Small N Coil Small A Coil Alternate Mounting Locations 6 ...

Page 7: ...C04014 Fig 3C Fan Coil Mounting Locations 208 230 v Application Sloped Fan Coil A Coil in Fan Coil Single Lamp Application Sloped Fan Coil Dual Lamp Application 7 ...

Page 8: ... 2018 CAC BDP 7310 W Morris St Indianapolis IN 46231 8 Form No 00001398 Catalog No IM UVLCR 01 ...

Reviews: