Pump Configuration Menu – PUMPCONF
No. Name
Status
Default Unit Displayed text *
Description
1
hpumpseq
0 to 1
0
-
Condenser Pumps
Sequence
Condenser pumps sequence
2
cpumpseq
0 to 1
0
-
Cooler Pumps Sequence
Cooler pumps sequence
3
0 = No Pump
0 = no pump
4
1 = One Pump Only
1 = one pump only
5
pump_per
no/yes
no
-
Pump Sticking Protection
Pump anti-sticking protection
6
pump_sby
no/yes
no
-
Stop Pump During Standby Pump stopped during standby
7
pump_loc
no/yes
yes
-
Flow Checked If Pump Off Water flow is checked when the pump is off
8
stopheat
no/yes
no
-
Cooler Pump Off In Heat
Cooler pump is off when the unit is in Heating
9
stopcool
no/yes
no
-
Cond Pump Off In Cool
Condenser pump is off when the unit is in Cooling
*Displayed in English by default.
Reset Configuration Menu – RESETCFG
No. Name
Status
Default Unit Displayed text *
Description
1
cr_sel
0 to 4
0
-
Cooling Reset Select
Reset source in Cooling
2
hr_sel
0 to 4
0
-
Heating Reset Select
Reset source in Heating
3
0=None, 1=OAT
0 = None
1 = OAT
4
2=Delta T, 4=Space Temp 2 = Delta T
4 = Space temperature
5
3=4-20mA control
3 = 4-20 mA signal
6
7
Cooling
Cooling
8
oat_crno
-10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value
OAT, no reset value
(applies to units with a Dry Cooler at the condenser)
9
oat_crfu
-10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value
OAT, max. reset value
(applies to units with a Dry Cooler at the condenser)
10 dt_cr_no
0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value
Delta T, no reset value
11
dt_cr_fu
0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value
Delta T, max. reset value
12 v_cr_no
0 to 20
0
mA Current No Reset Value
Current, no reset value
13 v_cr_fu
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
14 spacr_no
-10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value
Space temperature, no reset value
15 spacr_fu
-10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value
Space temperature, max. reset value
16 cr_deg
-16.7 to 16.7
-30 to 30
0
0
^C
^F
Cooling Reset Deg. Value
Cooling reset value
17
18
Heating
Heating
19 oat_hrno
-10 to 51.7
14 to 125
-10
14
°C
°F
OAT No Reset Value
OAT, no reset value
(applies to units with a DryCooler at the condenser)
20 oat_hrfu
-10 to 51.7
14 to 125
-10
14
°C
°F
OAT Full Reset Value
OAT, max. reset value
(applies to units with a DryCooler at the condenser)
21 dt_hr_no
0 to 13.9
0 to 25
0
0
^C
^F
Delta T No Reset Value
Delta T, no reset value
22 dt_hr_fu
0 to 13.9
0 to 25
0
0
^C
^F
Delta T Full Reset Value
Delta T, max. reset value
23 v_hr_no
0 to 20
0
mA Current No Reset Value
Current, no reset value
24 v_hr_fu
0 to 20
0
mA
Current Full Reset Value
Current, max. reset value
25 spahr_no
-10 to 51.7
14 to 125
-10
14
°C
°F
Space T No Reset Value
Space temperature, no reset value
26 spahr_fu
-10 to 51.7
14 to 125
-10
14
°C
°F
Space T Full Reset Value
Space temperature, max. reset value
27 hr_deg
-16.7 to 16.7
-30 to 30
0
0
^C
^F
Heating Reset Deg. Value
Heating reset value
*Displayed in English by default.