64
Boldface
indicates field-supplied drive is required.
NOTES:
1. For more information, see General Fan Performance Notes on
2. Recommend using field-supplied fan pulley (part number
KR11AZ506), motor pulley (part number KR11HY1
8
1), and belt
(part number KR30AE041) with field-supplied drive.
Boldface
indicates field-supplied drive is required.
NOTES:
1. For more information, see General Fan Performance Notes on
2. Recommend using field-supplied fan pulley (part number
KR11AZ606) and belt (part number KR30AE037) with field-sup-
plied drive.
Table J — 50KC**05 4 Ton Vertical Supply (3 Phase)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
695
0.25
818
0.37
930
0.51
1032
0.66
1126
0.83
975
731
0.30
849
0.43
955
0.57
1053
0.72
1145
0.89
1050
769
0.36
880
0.49
982
0.63
1077
0.79
1166
0.97
1125
807
0.42
913
0.56
1011
0.71
1103
0.87
1188
1.05
1200
847
0.49
948
0.63
1042
0.79
1130
0.96
1213
1.14
1275
887
0.57
983
0.72
1073
0.88
1158
1.06
1239
1.24
1350
928
0.66
1020
0.82
1106
0.98
1188
1.16
1266
1.35
1425
969
0.76
1057
0.92
1140
1.09
1219
1.28
1295
1.48
1500
1010
0.87
1095
1.04
1175
1.21
1251
1.41
1325
1.61
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
1215
1.01
1298
1.21
1378
1.42
1454
1.64
1526
1.87
975
1231
1.08
1313
1.28
1390
1.49
1465
1.71
1536
1.94
1050
1249
1.16
1329
1.36
1405
1.57
1478
1.79
1547
2.03
1125
1270
1.24
1347
1.45
1421
1.66
1492
1.89
—
—
1200
1292
1.34
1367
1.54
1440
1.76
1509
1.99
—
—
1275
1315
1.44
1389
1.65
1459
1.88
1527
2.11
—
—
1350
1341
1.56
1412
1.77
1481
2.00
1547
2.23
—
—
1425
1367
1.68
1437
1.90
1504
2.13
—
—
—
—
1500
1395
1.82
1463
2.04
1528
2.28
—
—
—
—
Medium static 920-1303 RPM, 1.7 BHP max
High static 1208-1550 RPM, 2.9 BHP max
Table K — 50KC**06 5 Ton Horizontal Supply (1 Phase)
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
725
0.33
840
0.46
937
0.60
1023
0.75
1101
0.90
975
765
0.40
876
0.54
970
0.68
1054
0.84
1131
1.00
1050
806
0.48
912
0.63
1004
0.78
1087
0.94
1162
1.11
1125
847
0.57
950
0.72
1039
0.88
1120
1.05
1194
1.23
1200
889
0.66
988
0.83
1075
1.00
1154
1.18
1226
1.36
1275
931
0.78
1027
0.95
1112
1.13
1189
1.31
1260
1.50
1350
974
0.90
1067
1.08
1149
1.27
1224
1.46
—
—
1425
1018
1.03
1107
1.23
1187
1.43
—
—
—
—
1500
1061
1.19
1148
1.39
—
—
—
—
—
—
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
900
1172
1.06
1239
1.23
1302
1.40
—
—
—
—
975
1201
1.16
1267
1.34
1329
1.52
—
—
—
—
1050
1231
1.28
1296
1.46
—
—
—
—
—
—
1125
1262
1.41
—
—
—
—
—
—
—
—
1200
—
—
—
—
—
—
—
—
—
—
1275
—
—
—
—
—
—
—
—
—
—
1350
—
—
—
—
—
—
—
—
—
—
1425
—
—
—
—
—
—
—
—
—
—
1500
—
—
—
—
—
—
—
—
—
—
Medium static 1035-1466 RPM, 1.5 BHP max
Summary of Contents for Puron R-410A
Page 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Page 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Page 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Page 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Page 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Page 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Page 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...