
23
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of the
sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
CHANGING THE DIRTY SENSOR TEST
By default, sensor dirty test results are indicated by:
• The sensor’s Dirty LED flashing.
• The controller’s Trouble LED flashing.
• The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so that the
controller’s supervision relay is not used to indicate test results.
When two detectors are connected to a controller, sensor dirty
test operation on both sensors must be configured to operate in
the same manner.
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of the
sensor housing until the sensor’s Alarm LED turns on and
its Dirty LED flashes twice (approximately 60 seconds).
2. Reset the sensor by removing the test magnet then holding
it against the sensor housing again until the sensor’s Alarm
LED turns off (approximately 2 seconds).
REMOTE STATION TEST
The remote station alarm test checks a test/reset station’s abili-
ty to initiate and indicate an alarm state.
SD-TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns on.
3. Reset the sensor by turning the key switch to the RESET/
TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns off.
REMOTE TEST/RESET STATION DIRTY SENSOR TEST
The test/reset station dirty sensor test checks the test/reset sta-
tion’s ability to initiate a sensor dirty test and indicate the re-
sults. It must be wired to the controller as shown in Fig. 31 and
configured to operate the controller’s supervision relay. For
more information, see “Changing the dirty sensor test” opera-
Fig. 31 — Remote Test/Reset Station Connections
Dirty Sensor Test Using an SD-TRK4
1. Turn the key switch to the RESET/TEST position for two
seconds.
2. Verify that the test/reset station’s Trouble LED flashes.
Table 2 — Dirty LED Test
FLASHES
DESCRIPTION
1
0-25% dirty (Typical of a newly installed detector)
2
25-50% dirty
3
51-75% dirty
4
76-99% dirty
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and
authority concern.
Changing the dirty sensor test operation will put the detector
into the alarm state and activate all automatic alarm responses.
Before changing dirty sensor test operation, disconnect all
auxiliary equipment from the controller and notify the proper
authorities if connected to a fire alarm system.
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and
authority concern.
This test places the duct detector into the alarm state. Unless
part of the test, disconnect all auxiliary equipment from the
controller before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper authorities
before performing the test.
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and
authority concern.
If the test/reset station’s key switch is left in the RESET/TEST
position for longer than seven seconds, the detector will
automatically go into the alarm state and activate all automatic
alarm responses.
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel and
authority concern.
Holding the test magnet to the target area for longer than
seven seconds will put the detector into the alarm state and
activate all automatic alarm responses.
1
12
14
13
19
15
2
20
3
RESET/TEST
Trouble
POWER
ALARM
SUPERVISION RELAY
CONTACTS [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 VDC (-)
18 VDC (-)
AUXILIARY
EQUIPMENT
+
−
WIRE MUST BE
ADDED BY
INSTALLER
SMOKE DETECTOR
CONTROLLER
Summary of Contents for Puron R-410A
Page 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Page 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Page 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Page 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Page 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Page 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Page 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...