Operation and Maintenance Manual
NOTE:
Read all instructions and data in this manual before operating.
Fig. 1 – FN1SXF
A Note About Safety
About the Negative Air Machine/Air Scrubber
The OptiClean™ is a portable solution primarily designed to help
convert normal hospital rooms into Airborne Infectious Isolation Rooms
(AIIR). Designed to ASHRAE’s Standard 170 for Ventilation of Health
Care Facilities, the OptiClean™ uses highly efficient filters and a heavy
duty, to remove contaminated air from the room. The resulting negative
air pressure, or “vacuum effect,” helps limit the spread of air-based
contaminants into surrounding areas.
If negative pressure is not required, such as in an open-air temporary
hospital, business or home, the machine can be used as an air “scrubber,”
pulling air in, removing many contaminants, and discharging cleaner air
Any time you see this symbol
in manuals, instructions and on the
unit, be aware of the potential for personal injury. There are three levels
of precaution:
DANGER
identifies the most serious hazards which will result in severe
personal injury or death.
WARNING
signifies hazards that could result in personal injury or
death.
CAUTION
is used to identify unsafe practices which would result in
minor personal injury or product and property damage.
NOTE
is used to highlight suggestions which will result in enhanced
installation, reliability, or operation.
back into the room.
The OptiClean™ negative air machine features:
•
99.97% efficient long-life HEPA filter removes particles as small as
0.3 microns
•
Standard MERV 7 pre-filter
•
Nominal 500 CFM
•
According to ASHRAE Standard 170: Ventilation of Health Care
Facilities
•
Portable and adaptable to nearly any location
•
Heavy duty locking casters for easy and smooth transport
•
HEPA filter rack and sealing design meet air leakage requirement
•
Red lighted indicator to alert user when filters are overloaded
(generally means pre-filter requires replacement)
•
Green ON/OFF switch illuminates to verify when running
•
3 meters long power cord with strain relief
•
Power cable access from rear of the unit, with optional plug
•
230V / 1Ph - 50 / 60Hz
•
Galvanized steel, powder paint cabinet is fully insulated
•
Exhaust transition plate to standard
FN1SXF
OptiClean™ Negative Air Machine and Scrubber
!
WARNING
PERSONAL INJURY OR PROPERTY DAMAGE
HAZARD
Failure to follow this warning could result in personal injury or
property damage.
Improper installation, adjustment, alteration, service, maintenance, or
use can cause conditions which may cause personal injury or property
damage. Consult a qualified installer or your distributor for information
or assistance. Read and follow all instructions and warnings, including
labels shipped with or attached to unit before operating.
!
WARNING
PORTABLE UNIT AND METAL SHARP EDGES
HAZARD
Failure to follow this Warning could cause personal injury or death.
This unit must be used in a location where unsupervised children are
not allowed to play. The unit is portable, and areas inside and under the
unit could cause personal injury. If the unit is used in a horizontal
configuration, physical barriers must be installed around the unit to
prevent unauthorized access.
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect all electrical power to the unit before removing access
panels to perform any maintenance.
If the supply cord is damaged, it must be replaced by the manufacturer,
its service agent or similarly qualified persons in order to avoid a
hazard.
!
WARNING
PERSONAL PROTECTION
This appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been
given supervision or instruction concerning use of the appliance by a
person responsible for their safety.