FN1AAF: Operation and Maintenance Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

Airflow Adjustments

For  models  006  and  015,  if  you  desire  different  airflows  from  the

factory-set Low, Medium, and High (taps 1, 3, and 5), do these steps:

1. Move the power switch to the OFF position.
2. Unplug the unit from the wall outlet.
3. Listen  to  make  sure  the  blower  wheel  has  stopped  spinning,  and

loosen

 the screws attaching the bottom door, but do 

not

 remove.

4. Remove the screws attaching the upper door and allow it to gently

swing down and rest, supported by the wire harness attached to the

front panel.

5. Locate  the  three  blower  speed  tap  wires  (red,  blue,  and  gray)

attached to the blower motor (

Fig. 6

).

6. Identify the correct Motor Tap for desired airflows and connect the

wires according to 

Table 2

.

– The Red motor lead is energized when switch is set to LOW, the

Blue motor lead is energized when switch is set to MED.

NOTE: 

The Blue and Gray motor leads are energized when switch is set

to HIGH. The 

Gray lead should remain on Motor Tap 5 

in order to

assure  that  red  filter/obstruction  indicator  is  properly  detecting  filter

condition.

A200258

Fig. 6 – Motor Taps

7. Replace the top door screws.
8. Tighten the bottom door screws.

Table 2 – Blower Configuration

Altitude Adjustments

Depending  on  your  location,  you  may  see  up  to  10%  increase  of

measured  airflow  at  higher  altitudes. To  compensate,  you  can  change

motor taps for alternate airflows 

(Airflow Adjustments on p4)

.

Troubleshooting

Before  you  request  dealer  service,  check  for  these  easily  solved

problems: 

• Check your main electrical panel circuit breakers or fuses if the unit

will not turn on.

• Make sure the unit is plugged in to a working 115V electrical outlet.

• Check for sufficient airflow. Filters should be clean and unobstructed.
If you need to contact your authorized dealer for troubleshooting and/or

repairs, be sure to have the model and serial numbers of your equipment

available.

Specifications

A200223

Fig. 7 – 005 Model Wiring Diagram

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect  all  electrical  power  to  the  unit  before  removing  access

panels to perform any maintenance.

Switch Setting

Motor Lead

Motor Tap Options

LOW

Red

1
2
3

Switch Setting

Motor Lead

Motor Tap Options

MED

Blue

2
3
4

Switch Setting

Motor Lead

Motor Tap Options

HIGH

Gray

5

Table 3 – Electrical Specifications

005 Model

006 Model

015 Model

Voltage

115

Hertz

60

Amps

5.0

12.0

Speeds

*

*.

005 model

 has a green lighted power switch only; wired to tap 5 from the 

factory.

006 and 015 models

 have the green lighted power switch, plus 3-speed 

rotary switch; wired to taps 1, 3, and 5 from the factory. Taps 2 and 4 can be 

field-wired for alternative CFMs. See 

(Airflow Adjustments on p4)

1

3

Nominal CFM

500

200 / 400 / 600

500 / 1000 / 1500

BRN 

BLK - L

YEL

 - N

GRN/YEL

 - GND

BLU - 3

FM

TRAN

115V

FILTER

LIGHT

DIFFERENTIAL

PRESSURE

SWITCH

C

R

2

1

2a

1a

N

L1

POWER PLUG

LIGHTED

POWER SWITCH

24V

Summary of Contents for OptiClean FN1AAF Series

Page 1: ...print compared to many competitors and can be mounted and operated horizontally when necessary Portable and adaptable to nearly any location Heavy duty locking casters for easy and smooth transport HEPA filter rack and sealing design meet air leakage requirement Red lighted indicator to alert user when filters are overloaded generally means pre filter requires replacement Green ON OFF switch illum...

Page 2: ...iling register box etc purchased or fabricated on site to complete a path for the air to exhaust from the negative air area Caulk or tape all seams Run the flexible duct per applicable codes and requirements with no hard bends or obstructions 8 Remove the bottom front door then the top door over the blower section Inspect the HEPA filter and make sure it has not been dislodged or damaged during sh...

Page 3: ... 40 000 hours of operation or 4 years under normal conditions and with recommended replacement of the pre filter air scrubber use will reduce filter life If the red indicator light is illuminated and did not extinguish after replacing the pre filter then the next step is to replace the main HEPA filter For residential use call your dealer to do this procedure For healthcare facilities follow these...

Page 4: ...rflow at higher altitudes To compensate you can change motor taps for alternate airflows Airflow Adjustments on p4 Troubleshooting Before you request dealer service check for these easily solved problems Check your main electrical panel circuit breakers or fuses if the unit will not turn on Make sure the unit is plugged in to a working 115V electrical outlet Check for sufficient airflow Filters sh...

Page 5: ... RED BLU GRY RED BLU GRY BLK YEL GRN YEL BLK BRN 24V BLK 11 12 14 24 21 G 1 2 3 7 6 8 4 9 11 12 14 15 16 17 18 19 10 5 13 Item Qty Description Part Number Model Size 005 006 015 1 1 Discharge Transition Plate 346303 701 346303 702 2 1 Power Cord 346284 401 3 1 Strain Relief 346294 401 4 1 Motor HD46AM126 HD46AM127 HD52AM120 5 1 Blower Housing Assembly 342890 75103 342890 75105 6 2 Gasket 6 152 mm ...

Page 6: ...dition Date 08 20 Catalog No OM FN1AAF 03 Replaces OM FN1AAF 02 FN1AAF Operation and Maintenance Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Notes Page ...

Reviews: