FN1AAF: Operation and Maintenance Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

Unpacking Your System

Carefully remove your unit from its packaging. Inspect for damage. If

damage is noted, contact your shipping carrier and file a claim.

Assemble the Unit

1. Remove the parts bags and/or box from the lower compartment.
2. Lay the unit on  its back,  as near as possible to  its intended  final

location.

NOTE: 

The  unit  can  be  operated  without  casters,  on  its  back  in  a

horizontal orientation, as long as there is sufficient space at either end for

air intake and output. Make sure to properly strap or otherwise secure it

to a base to avoid unintentional movement.
When the unit is mounted horizontally, an additional pre-filter must be

used. See 

Table 1

.

3. Attach the caster assemblies (ref 

Fig. 2

) to the bottom of the unit.

a. Remove the screws from the outer corners of the cabinet bottom.

b. Position the caster assembly along the outer edge of the unit and 

line up the screw holes.

c. Use the removed screws to attach the caster assembly.

d. Repeat for the other side.

A200233

Fig. 2 – Boxed Casters and Duct Transition (10-inch round shown)

4. Use the included screws to attach the round or oval duct transition

plate  to  the  top  of  the  unit  (

Fig. 3

). 

NOTE

: The  transition  plate

must

 be installed even if the unit is being used as an air scrubber.

An optional air diffuser (KFADG0101SML/LRG) is also available

for air scrubber use.

5. Carefully  lift the  unit  to  a vertical position  on  its casters. HINT:

Lock the casters before lifting or tilting up the unit.

6. Move the unit in its final position and lock all four casters.
7. For negative-air setup, do these steps. If used as an  air scrubber,

skip to step 8.

a. Use a compression clamp to attach 10- or 12-inch round flexible 

ducting (supplied by others) to the transition plate on top of the 

unit.

b. Run the flexible ducting as recommended by the mechanical plan 

and attach to a transition piece (ceiling register box, etc., 

purchased or fabricated on site) to complete a path for the air to 

exhaust from the negative-air area. Caulk or tape all seams. Run 

the flexible duct per applicable codes and requirements, with no 

hard bends or obstructions.

8. Remove the bottom front door, then the top door over the blower

section.  Inspect  the  HEPA  filter  and  make  sure  it  has  not  been

dislodged or damaged during shipping, that the side bolts and nuts

near each corner are tight and the HEPA filter is held securely in

place, and the seal around the top edge of the filter is in place.

9. Make sure the first-stage pre-filter is in place and not damaged.
10. Replace the top door over the blower, then the bottom front door.
11. Plug the unit into a grounded 115V outlet.

A200218

Fig. 3 – Typical Duct Transition Installation

Operating Instructions

IMPORTANT: 

Always lock the casters during operation. 

IMPORTANT: 

Make sure there are no paper or lightweight loose 

objects near the floor by the unit that could be sucked into the bottom air 

intake or front opening of the bottom front door. We recommend that you 

regularly clean or sweep the floor around the unit to extend the life of the 

pre-filter.

• Locate the control panel on the front upper left (

Fig. 4

).

• Rock  the  green  ON/OFF  switch  up  to  the  ON  position.  It  should

illuminate. There will be a slight delay before air begins to move as

the blower motor has a built-in 3-second operational delay. 

• For the 006 and 015 models, select the fan speed desired.

• Observe the unit running for a short time to make sure there are no

unusual  noises,  that  air  is  freely  flowing  through  the transition  and

ducting, and the unit is not shifting position. Make sure the casters are

locked!

A200222

Fig. 4 – Control Panels

WARNING

!

TIP OVER HAZARD

Failure  to  follow  this  warning  could  result  in  personal  injury  and/or

property damage.

Unit must be on a smooth and solid surface. When moving the unit:

-

make sure the path is free of obstacles

-

make sure the wheels are unlocked

-

place hands around the center of the unit and move slowly

Table 1 – Horizontal Configuration Pre-Filters (cartons of 12)

OptiClean Model

Pre-Filter Part No.

FN1AAF005, FN1AAF006

KFAFK0212MED

FN1AAF015

KFAFK0312LRG

005

006 / 015

Summary of Contents for OptiClean FN1AAF Series

Page 1: ...print compared to many competitors and can be mounted and operated horizontally when necessary Portable and adaptable to nearly any location Heavy duty locking casters for easy and smooth transport HEPA filter rack and sealing design meet air leakage requirement Red lighted indicator to alert user when filters are overloaded generally means pre filter requires replacement Green ON OFF switch illum...

Page 2: ...iling register box etc purchased or fabricated on site to complete a path for the air to exhaust from the negative air area Caulk or tape all seams Run the flexible duct per applicable codes and requirements with no hard bends or obstructions 8 Remove the bottom front door then the top door over the blower section Inspect the HEPA filter and make sure it has not been dislodged or damaged during sh...

Page 3: ... 40 000 hours of operation or 4 years under normal conditions and with recommended replacement of the pre filter air scrubber use will reduce filter life If the red indicator light is illuminated and did not extinguish after replacing the pre filter then the next step is to replace the main HEPA filter For residential use call your dealer to do this procedure For healthcare facilities follow these...

Page 4: ...rflow at higher altitudes To compensate you can change motor taps for alternate airflows Airflow Adjustments on p4 Troubleshooting Before you request dealer service check for these easily solved problems Check your main electrical panel circuit breakers or fuses if the unit will not turn on Make sure the unit is plugged in to a working 115V electrical outlet Check for sufficient airflow Filters sh...

Page 5: ... RED BLU GRY RED BLU GRY BLK YEL GRN YEL BLK BRN 24V BLK 11 12 14 24 21 G 1 2 3 7 6 8 4 9 11 12 14 15 16 17 18 19 10 5 13 Item Qty Description Part Number Model Size 005 006 015 1 1 Discharge Transition Plate 346303 701 346303 702 2 1 Power Cord 346284 401 3 1 Strain Relief 346294 401 4 1 Motor HD46AM126 HD46AM127 HD52AM120 5 1 Blower Housing Assembly 342890 75103 342890 75105 6 2 Gasket 6 152 mm ...

Page 6: ...dition Date 08 20 Catalog No OM FN1AAF 03 Replaces OM FN1AAF 02 FN1AAF Operation and Maintenance Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Notes Page ...

Reviews: