28
Table 11 — Evaporator Fan Performance — 50XCA08 Units
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure
NOTES:
1. Units are available with several motor hp options. Refer to Table 1.
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan perfor-
mance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on 1 in. standard throw-away filter, unit
casing, and wet DX (direct expansion) coil losses at sea level.
CFM
ESP (in. wg)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2200
497 0.27 581 0.39 655 0.52 722 0.66
782 0.80
839 0.95
892 1.11
941 1.28
989 1.45 1034 1.62
2400
542 0.35 621 0.48 690 0.62 753 0.77
812 0.92
866 1.08
917 1.25
966 1.42 1012 1.60 1056 1.78
2600
587 0.45 660 0.59 726 0.74 787 0.89
843 1.06
895 1.22
945 1.40
992 1.58 1037 1.76 1080 1.95
2800
632 0.56 701 0.71 763 0.87 821 1.04
875 1.21
925 1.38
974 1.57 1019 1.75 1063 1.95
—
—
3000
677 0.69 742 0.85 801 1.02 856 1.19
908 1.37
957 1.56 1003 1.75 1048 1.95
—
—
—
—
3200
723 0.84 783 1.01 839 1.19 892 1.37
942 1.56
989 1.76 1034 1.96
—
—
—
—
—
—
3400
768 1.01 825 1.19 879 1.37 929 1.57
977 1.77 1023 1.97
—
—
—
—
—
—
—
—
3600
813 1.19 867 1.39 918 1.58 967 1.79 1013 2.00
—
—
—
—
—
—
—
—
—
—
CFM
ESP (in. wg)
1.00
1.10
1.20
1.30
1.40
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
2200
1077 1.80 1119 1.98
—
—
—
—
—
—
2400
1099 1.97
—
—
—
—
—
—
—
—
2600
—
—
—
—
—
—
—
—
—
—
2800
—
—
—
—
—
—
—
—
—
—
3000
—
—
—
—
—
—
—
—
—
—
3200
—
—
—
—
—
—
—
—
—
—
3400
—
—
—
—
—
—
—
—
—
—
3600
—
—
—
—
—
—
—
—
—
—