Battery
10-year Lithium CR123A battery ensures the following data is retained for a
maximum of 720 hours during power outages:
•
Time
•
Graphics
•
Control programs
•
Editable properties
•
Schedules
•
Trends
To conserve battery life, you can set the driver to turn off battery backup after a
specified number of days and depend on the archive function to restore data
when the power returns.
A low battery is indicated by the
Battery Low
LED or a low battery alarm in the i-
Vu® application, a touchscreen device, and Field Assistant.
Protection
Built-in surge and transient protection for power and communications in
compliance with EN61000-6-1.
Incoming power is protected by a replaceable 3 Amp Pico® fuse. Network
connections are protected by non-replaceable internal solid-state polyswitches
that reset themselves when the condition that causes a fault returns to normal.
The power, network, input, and output connections are also protected against
transient excess voltage/surge events lasting no more than 10 msec.
CAUTION
To protect against large electrical surges on serial EIA-485
networks, place a PROT485 at each place wire enters or exits the building.
BT485 connector
You can install a BT485 (#BT485 - sold separately) to an MPC Open XP at the
beginning and end of a network segment to add bias and to terminate a network
segment.
Status indicators
LEDs indicate status of communications and low battery status. Seven segment
display indicates running, error, and power status.
Environmental operating
range
0 to 140° F (-18 to 60°C), 0 to 90% relative humidity, non-condensing
Storage temperature range
-24 to 140°F (-30 to 60°C), 0 to 90% relative humidity, non-condensing
Physical
Rugged aluminum cover, removable screw-type terminal blocks