background image

Installing the MPC Open XP 

 

 

 

 

 

MPC Open XP 

MPC Open XPIO48/816 

 

CARRIER CORPORATION ©2019   

Installation and Start-up Guide 

 

All rights reserved 

 

 

 

Use the power supply only for Carrier controllers. 

 

To wire for power 

Turn off the MPC Open XP's power switch to prevent it from powering up before you can verify the correct 

voltage. 

Remove primary power from the 24 Vac transformer. 

Pull the screw terminal connector from the controller's power terminals labeled 

Return

 and 

24 Vac/26 Vdc

Connect the transformer wires to the screw terminal connector. 

Apply primary power to the transformer. 

Measure the voltage at the controller's power screw terminal connector to verify that the voltage is within the 

operating range of 21.6 - 26.4 Vac.  

Insert the screw terminal connector into the controller's power terminals. 

Turn on the MPC Open XP's power switch. 

Verify that the Power LED is on and the Run LED is blinking. 

 
 

 

Addressing the MPC Open XP 

The MPC Open XP's two rotary switches determine its MAC address when it is placed on a BACnet MS/TP network. 

The rotary switches define the MAC address portion of the device's BACnet address, which is composed of the 

network address and the MAC address. 

Turn on the controller's power. 

Using the rotary switches, set the controller's address. Set the 

Tens

 (

10's

) switch to the tens digit of the 

address, and set the 

Ones

 (

1's

) switch to the ones digit. 

EXAMPLE

  If the controller’s address is 25, point the arrow on the 

Tens

 (

10's

) switch to 2 and the arrow on 

the 

Ones

 (

1's

) switch to 5. 

10's

1's

1

3

45

2

7

8

9

6

0

1

3

45

2

7

8

9

6

0

  

Turn on the controller's power.  

NOTE

  The controller reads the address each time you apply power to it. 

 CAUTION

  The factory default setting is 

00

 and must be changed to successfully install your MPC Open XP. 

 
  
 

 

Summary of Contents for MPC Open XP Series

Page 1: ...n X XP PI IO O4 48 8 8 81 16 6 I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2019 A member of the United Technologies Corporation family St...

Page 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2019 All rights reserved throughout the world i Vu is a registered tra...

Page 3: ...fications 15 Outputs 15 Output wiring specifications 16 To wire inputs and outputs 16 To use the Auto Off On switches 19 Wiring devices to the MPC Open XP s Rnet port 19 Rnet wiring specifications 20...

Page 4: ......

Page 5: ...and MPC Open XPIO expanders The Multipurpose Controller Open XP MPC Open XP OPN MPCXP provides monitoring and control for a variety of HVAC system applications The MPC Open XP supports multiple I O co...

Page 6: ...n XPIO48 OPN MPCXPIO48 and MPC Open XPIO816 OPN MPCXPIO816 are expanders that connect to the expandable MPC Open XP to increase the number of inputs and outputs To add inputs or outputs to the MPC Ope...

Page 7: ...the total power required by the sensors on the Rnet exceeds the power supplied by the Rnet port use an external power source The Wireless Adapter Equipment Touch or TruVu ET Display must be powered b...

Page 8: ...work connections are protected by non replaceable internal solid state polyswitches that reset themselves when the condition that causes a fault returns to normal The power network input and output co...

Page 9: ...40 VA power consumption 26 Vdc 25 V min 30 V max 21 W Single Class 2 source only 100 VA or less MPC Open XPIO816 24 Vac 10 50 60 Hz 45 VA power consumption 26 Vdc 25 V min 30 V max 21 W Single Class 2...

Page 10: ...ing range 20 to 140 F 29 to 60 C 10 90 relative humidity non condensing NOTE Install in a UL Listed enclosure only Storage temperature range 24 to 140 F 30 to 60 C 0 to 90 relative humidity non conden...

Page 11: ...uch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Screw the MPC Open XP into an enclosed panel using the...

Page 12: ...oller s power terminals 8 Turn on the MPC Open XP s power switch 9 Verify that the Power LED is on and the Run LED is blinking Addressing the MPC Open XP The MPC Open XP s two rotary switches determin...

Page 13: ...troller s ports and terminals To wire the controller to the network 1 Pull the screw terminal connector from the controller s power terminals labeled 24 Vac 26 Vdc and Return Ground 2 Check the commun...

Page 14: ...l connector into the MPC Open XP s power terminals 8 Turn on the MPC Open XP s power 9 Verify communication with the network by viewing a Module Status report in the i Vu interface See the Open Contro...

Page 15: ...Do not touch components or leads Handle the board by its edges Isolate from high voltage or electrostatic discharge Ensure that you are properly grounded Wiring restrictions for connecting the expand...

Page 16: ...away from the controller To wire the expander for power CAUTIONS The expanders are powered by a Class 2 power source Take appropriate isolation measures when mounting it in a control panel where non...

Page 17: ...der s address You must give the expanders an address that is unique on the expander network 1 If wired for power turn off the expander s power and the attached MPC Open XP s power 2 Set the expander s...

Page 18: ...y RTD 1 Platinum 1 kOhm at 32 F 0 C Nickel Iron 1 kOhm at 70 F 21 C Balco TS8000 1 kOhm at 70 F 21 C Input voltages should be from 0 6 1 2 V NOTE For improved accuracy Carrier recommends using an exte...

Page 19: ...g devices to the MPC Open XP s Rnet port page 19 Outputs The MPC Open XP and expanders have universal outputs that you can use as binary outputs or analog outputs The outputs support driving external...

Page 20: ...nce of actual wire For 2 conductor wires this is twice the cable length Acceptable voltage drop in the wire from the controller to the controlled device Resistance Ohms of the chosen wire gauge Maximu...

Page 21: ...the input wiring to the screw terminals on the controller or expander See figure below NOTES Connect the shield wire to the GND terminal with the ground wire For a loop powered 4 20 mA sensor wire th...

Page 22: ...terminals on the MPC Open XP and to the controlled device Connect the ground wire to the UO s Gnd terminal WARNING Binary outputs are powered 24 Vdc channels Dry contact binary outputs are not support...

Page 23: ...ise to increase the output WARNING The output potentiometer is NOT used for binary output channels For a binary output turn the potentiometer clockwise until it stops maximum output and leave it in th...

Page 24: ...th TC drain wire terminated at controller UL temperature rating 32 167 F 0 75 C Voltage 300 Vac power limited Listing UL NEC CL2P or better To wire ZS sensors to the controller ZS Sensors are thermist...

Page 25: ...al Red Black White Green 12V Rnet Rnet Gnd 4 Apply power to the MPC Open XP To wire the Wireless Adapter for wireless sensors WARNING Do not apply line voltage mains voltage to the Wireless Adapter Th...

Page 26: ...off the outer jacket of the Rnet cable s Do not nick the inner insulation Inner insulation Outer jacket Foil shield 25 in 6 cm Shield wire 3 Strip about 0 25 inch 0 6 cm of the inner insulation from...

Page 27: ...requires a 24 Vac power supply It is not powered by the Rnet If the Equipment Touch will be Daisy chained on the Rnet with ZS sensors or a Wireless Adapter use the standard 4 conductor Rnet wiring and...

Page 28: ...rify that the Enhanced Access DIP switch is set to Off 5 Turn on the MPC Open XP s power 6 Turn on the Equipment Touch To wire the TruVu ET Display WARNING Do not apply line voltage main 24 Vdc power...

Page 29: ...t complete the following procedures to successfully install your MPC Open XP into an i Vu Control System Use the Help in the referenced software for detailed descriptions of these procedures Equipment...

Page 30: ...erence Name if needed 6 Do one of the following If the control program is In the Control Program drop down list Select the control program Not in the Control Program drop down list a Click Add New b B...

Page 31: ...n device Rnet port Temporary or permanent user interface for start up 1 Requires a USB Link Part USB L 2 See the Equipment Touch Installation and Setup Guide for detailed instructions CAUTION If multi...

Page 32: ...tion or Field Assistant Help for instructions on obtaining a Modstat If you cannot determine the error from the Modstat contact Carrier Control Systems Support 2 The controller s memory is full In the...

Page 33: ...MPC Open XP has power BACnet Tx The MPC Open XP is transmitting data from BACnet Port BACnet Rx The MPC Open XP is receiving data from BACnet Port Archive Valid The controller s memory backup is vali...

Page 34: ...ystems Support To erase volatile memory data and restore factory default configuration settings 1 Turn off the MPC Open XP s power switch Make sure the address switches are not set to 0 0 2 Hold down...

Page 35: ...in the i Vu application You can purchase replacement batteries from any retailer that sells a CR 123A battery 1 Verify that the MPC Open XP s power is on 2 Using a small flathead screwdriver pry up ea...

Page 36: ...utput MPC Open XP If the Aux Power Out port is used verify that it is wired correctly See To wire inputs and outputs page 16 To replace the fuse 1 Turn off the MPC Open XP s power 2 If the fuse is on...

Page 37: ...y cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the in...

Page 38: ...n XP UC Open or AppController These channel assignments are NOT correct in the MPC Open XP When using 39m AHU applications in the MPC Open XP or expanders you must reassign the correct hardware channe...

Page 39: ...de Equipment Name Point Name 1 1 2 0 20 mA Left UI 1 1 2 Thermistor Dry contact RTD Middle 1 2 0 10 V Right 2 3 4 0 20 mA Left UI 2 3 4 Thermistor Dry contact RTD Middle 3 4 0 10 V Right 3 5 6 0 20 mA...

Page 40: ...ight 11 18 20 0 20 mA Left UI 11 18 20 Thermistor Dry contact RTD Middle 18 20 0 10 V Right 12 19 20 0 20 mA Left UI 12 19 20 Thermistor Dry contact RTD Middle 19 20 0 10 V Right Point Cable Universal...

Page 41: ...expander Project Name Location Controller Network Number MAC Address Aux Power Out 1 24 Vdc 2 24 Vdc Point Cable Universal Inputs G Input Type Jumper Position of Pins I O Sensor code Equipment Name Po...

Page 42: ...Middle 3 4 0 10 V Right 7 5 6 0 20 mA Left UI 7 5 6 Thermistor Dry contact RTD Middle 5 6 0 10 V Right 8 7 8 0 20 mA Left UI 8 7 8 Thermistor Dry contact RTD Middle 7 8 0 10 V Right Point Cable Univer...

Page 43: ...Sensor code Equipment Name Point Name 1 1 2 0 20 mA Left UI 1 1 2 Thermistor Dry contact RTD Middle 1 2 0 10 V Right 2 3 4 0 20 mA Left UI 2 3 4 Thermistor Dry contact RTD Middle 3 4 0 10 V Right 3 5...

Page 44: ...Left UI 11 5 6 Thermistor Dry contact RTD Middle 5 6 0 10 V Right 12 7 8 0 20 mA Left UI 12 7 8 Thermistor Dry contact RTD Middle 7 8 0 10 V Right 13 1 2 0 20 mA Left UI 13 1 2 Thermistor Dry contact...

Page 45: ...4 0 20 mA Left UO 2 0 10 Vdc Middle Relay Right 3 5 6 0 20 mA Left UO 3 0 10 Vdc Middle Relay Right 4 7 8 0 20 mA Left UO 4 0 10 Vdc Middle Relay Right 5 1 2 0 20 mA Left UO 5 0 10 Vdc Middle Relay R...

Page 46: ...TruVu ET Display C D 6 20 17 Appendix A MPC Open XP wire lists Caution added to not use 39m library applications with the MPC Open XP C TS CP E WB 2 23 17 Changed sensor and adapter name from WS to w...

Page 47: ...u can have with an Equipment Touch is 15 Local Access port removed BACview added Equipment Touch Battery added Equipment Touch and removed BACview C D LJ O Wiring devices to the Rnet port Changed from...

Page 48: ......

Page 49: ......

Page 50: ...CARRIER CORPORATION 2019 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 431 01 1 24 2019...

Reviews: