10. BACKUP OPERATION (EMERGENCY OPERATION)
This product offers backup modes of operation to tide over certain emergency situations. If a fault occurs in
one of the compressors, it is possible to operate the system on an emergency basis by operating only the
remaining compressor(s), (compressor backup operation).
If one of the outdoor units fails in a combined outdoor unit system, the system can be operated on an
emergency basis by keeping only the remaining outdoor unit(s), (outdoor unit backup operation).
Perform backup operation setting in accordance with the procedure described below.
10-1.Note for Backup Operation
The method of backup operation differs according to the contents of fault as shown in the table below.
Note 1:
Keep the number of backed-up outdoor units under compressor backup operation to one in the system
(single refrigerant line). For a three-compressor model, the backing up of two faulty compressors is
prohibited.
Note 2:
It is prohibited to combine compressor backup operation and outdoor unit backup operation.
Note 3:
With a two-outdoor unit system containing an MMY-MAP120
∗
(or MAP096
∗
) and an MMY-MAP072
∗
,
do not preform outdoor unit backup operation to back up the MMY-MAP120
∗
(or MAP096
∗
).
It could lead to compressor failure due to the abnormal operation.
Contents of fault
Method of backup operation
Setting procedure
Go to 11-2.
Compressor backup (see Note 1)
One of the compressors in the same unit fails (see Note 1)
Go to 11-3
Outdoor unit backup or cooling-
season outdoor unit backup (see
Notes 2 and 3)
All the compressors in the same unit fail
A fault occurs in a compressor motor coil (e.g. a layer short-circuit)
A fault occurs in a refrigerating cycle part, fan or related part, or electrical part
A fault occurs in a temperature sensor or pressure sensor
Faulty
Faulty
Example
Prohibited
Example
Prohibited
Backed-up compressor Backed-up compressor
Two backed-up compressors
Faulty
Faulty
Faulty
Example
Prohibited
Backed-up compressor
Backed-up outdoor unit
Faulty
MMY-MAP120
∗
(MMY-MAP096
∗
)
MMY-MAP072
∗
Example
Prohibited
Faulty
Backed-up outdoor unit
Summary of Contents for MMY-MAP0724FT6UL
Page 35: ...35 3 5 Parts Layout in Outdoor Unit 072 type Model MMY MAP0724FT...
Page 36: ...36 096 120 type Model MMY MAP0964FT MAP1204FT...
Page 37: ...37 3 6 Parts Layout in Inverter Assembly 208 230V model MMY MAP0724FT9UL...
Page 38: ...38 208 230V model MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 39: ...39 460V model MMY MAP0724FT6UL...
Page 40: ...40 460V model MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 41: ...41 3 7 Outdoor Inverter print circuit board 3 7 1 Interface P C board MCC 1606...
Page 42: ...42 3 7 2 Inverter P C board for compressor MCC 1595 A3 IPDU For 208 230V model MMY MAP 4FT9UL...
Page 43: ...43 3 7 3 Inverter P C board for compressor MCC 1596 A3 IPDU For 460V model MMY MAP 4FT6UL...
Page 44: ...44 3 7 4 Inverter P C board for fan motor MCC 1610 FAN IPDU...
Page 45: ...45 3 7 5 Noise Filter P C board MCC 1608 A B For 208 230V model MMY MAP 4FT9UL...
Page 46: ...46 3 7 6 Noise Filter P C board MCC 1625 A B C For 460V model MMY MAP 4FT6UL...
Page 195: ...195...
Page 197: ...197...
Page 257: ...257 15 EXPLODED DIAGRAM PARTS LIST Outdoor unit 15 1 MMY MAP0724FT9UL...
Page 258: ...258 15 1 MMY MAP0724FT9UL...
Page 262: ...262 15 1 Inverter Assembly MMY MAP0724FT9UL...
Page 264: ...264 15 2 MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 265: ...265 15 2 MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 269: ...269 15 2 Inverter Assembly MMY MAP0964FT9UL MMY MAP1204FT9UL...
Page 271: ...271 15 3 MMY MAP0724FT6UL...
Page 272: ...272 15 3 MMY MAP0724FT6UL...
Page 276: ...276 15 3 Inverter Assembly MMY MAP0724FT6UL...
Page 278: ...278 15 4 MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 279: ...279 15 4 MMY MAP0964FT6UL MMY MAP1204FT6UL...
Page 283: ...283 15 4 Inverter Assembly MMY MAP0964FT6UL MMY MAP1204FT6UL...